29
English
Installation Pr
oc
edur
e
Option
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
Function
Page
Use of external control
Setting the output of
external control
Ionizer
Buzzer control
Maximum filter
usage time
Indication
and
details
Indication Details Indication
Details
Indication Details Indication Details Indication Details Indication Details
2
0
Disuse
Slave, Existing Control
0
Thermo
on
0
Disuse
0
Use of
buzzer
2
1000
hours
1
On/Off
2
Off
3
Window
4
Disuse
Master, Existing
Control
5
On/Off
6
Off
7
Window
8
Disuse
Slave, Reverse Control
1
Operation
on
1
Use
1
Disuse
of
buzzer
6
2000
hours
9
On/Off
A
Off
B
Window
C
Disuse
Master, Reverse
Control
D
On/Off
E
Off
F
Window
Option
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Function
Page
Individual control with remote control
Heating setting
compensation
Reserved
Reserved
Cycle time of Swing
Indication
and
details
Indication Details Indication
Details
Indication Details
Indication Details
3
0 or 1
Indoor 1
0
Default
0
34
seconds
(default)
2
Indoor 2
1
2°C
1
30
seconds
3
Indoor 3
2
5°C
2
38
seconds
4
Indoor 4
• By SEG4 setting, Minimizing fan operation when thermostat is off.
– Fan operates for 20 seconds at an interval of 5 minutes in Heat mode.
– Fan stops or operates Ultra low in Cooling when thermostat is off.
• Even if you set the Use of drain pump (SEG8) option to 0, it is automatically set to 2 (the drain pump is used with 3
minute delay).
• If you set the Maximum filter usage time (SEG18) option to a value other than 2 and 6, it is automatically set to 2
(1000 hours).
• If you set the Individual control with remote control (SEG20) option to a value other than 0 to 4, it is automatically set
to 0 (Indoor 1).
•