15
English
Installation Pr
oc
edur
e
• Do not apply force to the piping on the unit side when
connecting the drain hose. The hose should not be
allowed to hang loose from its connection to the unit.
Fasten the hose to a wall, frame or other support as
close to the unit as possible.
Ceiling
Support pieces
1 to 1.5 m
1/100 or more
• Install
horizontally.
Indoor unit
Be horizontal
Flexible hose
• Max. allowable axis gap
Max. 20 mm
Indoor unit
• Max. allowable bending angle
đɇуߥߢઘ
Indoor unit
NOTE
• If a concentrated drain pipe is installed, refer to the
figure below.
Centralized horizontal drain pipe
(more than 1/100 slope)
Main drain pipe
Full thread bolt hanger
1000 to 1500 mm
550 mm or
less
200 mm
or more
Individual
air vent
Main air vent
(must be installed)
• If 3 or more units are installed, install the main air vent
at the front of the farthest indoor unit from the main
drain pipe.
• To prevent water from flowing back to indoor units, install
an individual air vent at the top of each indoor unit.
– The air vents should be T or 7 shaped to prevent
dust or foreign substances from entering.
– You may not need to install air vent if the horizontal
drain pipe is in proper slope.