Setting an indoor unit address and installation option
Setting an indoor unit installation option
In order to check and set the indoor unit installation option code use the wired remote controller and
follow the directions below.
1.
Press the
and
buttons at the same time for more than 3 seconds and then a Main menu will be
displayed.
2. Press the
/
button to select and then press
button to enter a Sub-menu setting screen.
3.
Press the
/
button to select and then press
button to enter a Indoor unit installation option
code setting screen.
4.
Press the
/
button to set the installation option code in order. Press
button to go to the next
page.
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
2
RESERVED
Exterior
temperature sensor
Central control
RESERVED
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
Drain pump
RESERVED
RESERVED
RESERVED
Master / Slave
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
External control
External control
output
S-Plasma ion
Buzzer
Number of hours
using filter
SEG19
SEG20
SEG21
-
-
-
3
Individual control of
a remote controller
Heating setting
compensation
-
-
-
•
The first digit represents the page number and the remaining five digits are installation option.
•
The total option codes are 24 digits. You can set six digits at a time and it is distinguished by page
number (0, 1, 2, 3).