34
Adjusting air flow
Static Pressure
(mmAq)
0≤ SP ≤2.5
2.5< SP ≤5
5< SP ≤7.5
7.5< SP ≤10
Model
Option code for indoor unit
AJ12FBMDEC
01B062-1C0084-
272300-374000
01B062-1C00EB-
272300-374000
01B062-1C0552-
272300-374000
01B062-1C05CA-
272300-374000
With its phase control motor, you can adjust the indoor unit fan speed depending on the installation condition.
If the external static pressure is high so that the duct becomes longer or if the external static pressure is low so that
the duct becomes shorter, adjust the fan speed by referring the following table.
E. S. P(External Static Pressure) setting for phase control motor
•
represents E. S. P(External Static Pressure) range of factory setting.
You don’t have to adjust the fan speed separately if the external static pressure of the installation place is in
. When it is out of
, input the appropriate option code.
•
If you input the inappropriate option code, error may occur or the air conditioner is out of order. The
option code must be inputted correctly by the installation specialist or service agent.
Static Pressure
(mmAq)
0≤ SP ≤3
3< SP ≤6
6< SP ≤9
9< SP ≤12
12< SP ≤15
Model
Option code for indoor unit
AJ18FBMDEC
01B062-1C047F-
273200-372000
01B062-1C05D5-
273200-372000
01B062-1C092B-
273200-372000
01B062-1C0A71-
273200-372000
01B062-1C0AC8-
273200-372000
•
If the coil is not dry, run the unit for 2 hours with fan only to dry the coil.
•
The air filter is properly attached into the air passage on the air suction side of the air conditioning unit.
• Adjust the dampers so that each air inlet and outlet exhusts the designed airflow rate.
• If using booster fans(an outdoor air processing unit or ERV via duct), do not use automatic air-volume function.
• If the duct configurations have been changed, automatic air-volume function perform again.
• The product can be used within the range of rated voltage 220 V/230 V/240 V ± 5 V. If the product needs to be
installed in the condition that is out of the rated voltage stated above, additional setting with installation option is
required.