20
3-3-3. Plate type heat exchanger PHE
1) Power off before starting on work.
2) Close the valve connected to inlet/outlet of main water pipe.
3) Drain all water of water pipe connected to DVM CHILLER.
4) Unscrews the screw of inlet/outlet water pipe flange connected
to DVM CHILLER.
5) Unscrews the fixed screw of CABINET FRONT.
6) Separates wire of cycle parts connected to ASSY PHE from C-BOX.
7) Connect the refrigerant reclaimer in the charging port,
Recovering the refrigerant sealed in the product.
Use only charging port charging, recovery of refrigerants.
8) Separate the four points of the pipe connected to ASSY PHE
by welding .