4-2. What to check before diagnosis
4-2-1. Lamp combination expression method DISPLAY
■
Slim 1-Way & 2-Way cassette type
▶ Error detection and restart
■
1. If an error occurs during operation, it will be indicated by a flickering LED and all operations excluding the LED will stop.
■
2. When restarting with the remote control or switch, the error mode will be determined after normal operation.
▶ LED lamp display during error detection
Abnormal condition
Error
code
LED Display
Green
Red
Indoor temperature Sensor error (Open/Short)
E121
×
×
◑
×
×
1. Eva‑In Sensor error (Open/short)
2. Eva‑out Sensor error (Open/short)
E122
E123
◑
×
◑
×
×
Indoor Fan error
E123
◑
×
×
◑
×
1. If there is no communication between FCU
↔
repeater for 2
minutes
2. Communication Error received from repeater
3. Repeater Tracking 3 minute Error
4. Communication error after Tracking due to unmatching
number of installed units
5. Error due to duplicated communication address
6. Communicated address unconfirmed, communication error for
outdoor units excluding the ones above
E101
E102
E202
E201
E108
E109
×
×
◑
◑
×
Self‑diagnosis error display
1. Water temperature increase prevention error (product will stop
at high water temperatures of more than 65℃)
2. Thermal Fuse Open Error
E128
E198
×
×
◑
◑
◑
Floating S/W secondary detection
E153
×
×
×
◑
◑
EEPROM error
E162
◑
◑
◑
◑
◑
EEPROM option error
E163
◑
◑
◑
◑
◑
◑
Flickering × Off
※ All displays will be turned off if operation is stopped during error display.
※ If restarting, the error will be re‑determined after initial normal operations and error will be displayed again.
※ If error E108 occurs, reset the address and then reset the system.
Ex) If both #1 and #2 fan coil units are set as 5, #1 will change to #5 and E108, A002 will be displayed on #2