Field Setting Value
Main Menu &
Code
Sub Menu Function
Description
Sub
Code Default
Min
Max
Step
Unit
Water Law
Code 20∗∗
Outdoor Temp for Water Law
(Heating)
Point
1
∗∗11
-10
-20
5
1
˚C
Point
2
∗∗12
15
10
20
1
˚C
Water Out Temp for WL1
Heating (WL1-Floor)
Point
1
∗∗21
40
17
55
1
˚C
Point
2
∗∗22
25
17
55
1
˚C
Water Out Temp for WL2
Heating (WL2-Fan Coil Unit)
Point
1
∗∗31
50
17
55
1
˚C
Point
2
∗∗32
35
17
55
1
˚C
Heating Water Law for Auto
Mode
WL Type
∗∗41
1(WL1)
1
2
-
-
Outdoor Temp for Water Law
(Cooling)
Point
1
∗∗51
30
25
35
1
˚C
Point
2
∗∗52
40
35
45
1
˚C
Water Out Temp for WL1
Cooling (WL1-Floor)
Point
1
∗∗61
25
5
25
1
˚C
Point
2
∗∗62
18
5
25
1
˚C
Water Out Temp for WL2
Cooling (WL2-Fan Coil Unit)
Point
1
∗∗71
18
5
25
1
˚C
Point
2
∗∗72
5
5
25
1
˚C
Cooling Water Law for Auto
Mode
WL Type
∗∗81
1(WL1)
1
2
-
-
External Thermostat
Application
#1(Floor)
∗∗91
0(No)
0
2
1
-
#2(FCU)
∗∗92
0(No)
0
2
1
-
Water Law for Heating
•
Outdoor air temperature range : Lower limit
1
(#2011, Default -10˚C, Range : -20 ~ 5˚C),
Upper limit
2
(#2012, Default 15˚C, Range : 10 ~ 20˚C)
– With this default settings, the water outlet temperature by heating water law can be changed
within the outdoor temperature range of -10 ~ 15˚C.
•
Water out temperature range for floor/FCU applications respectively :
Upper limit
1
(#2021/2031, Default 40/50˚C, Range : 17 ~ 55˚C),
Lower limit
2
(#2022/2032, Default 25/35˚C, Range : 17 ~ 55˚C)
– With this default settings, the water outlet temperature by heating water law can be changed
within the range of 25/35 ~ 40/50˚C.
•
Type of water law for according to heating devices(floor/FCU) : #2041(Default “1”(WL1 for floor)),
“2”(WL2 for FCU or radiator)
Water Law for Cooling
•
Outdoor air temperature range : Lower limit
1
(#2051, Default 30˚C, Range : 25 ~ 35˚C),
Upper limit
2
(#2052, Default 40˚C, Range : 35 ~ 45˚C)
– With this default settings, the water outlet temperature by cooling water law can be changed
within the outdoor temperature range of 30 ~ 40˚C.
•
Water out temperature range for floor/FCU applications respectively :
Upper limit
1
(#2061/2071, Default 25/18˚C), Lower limit
2
(#2062/2072, Default 18/5˚C)
– With this default settings, the water outlet temperature by cooling water law can be changed
within the range of 5/18 ~ 18/25˚C.
•
Type of water law for according to cooling devices(floor/FCU) : #2081(Default “1”(WL1 for floor),
“2”(WL2 for FCU or radiator)