ENGLISH-39
02
INST
ALL
ATION
Types of allowable current
Conductors of supply cord shall have a nominal cross-sectional area not less than that shown in the table below .
Minimum cross-sectional area of conductors
Rated current of appliance (A)
Nominal cross-sectional area (mm2)
≤0 .2
Tinsel cord
a)
≤0 .2 and ≤3
0 .5
a)
>3 and ≤6
0 .75
>6 and ≤10
1 .0(0 .75)
b)
>10 and ≤16
1 .5(1 .0)
b)
>16 and ≤25
2 .5
>25 and ≤32
4
>32 and ≤40
6
>40 and ≤63
10
Exterior connection
DHW Power IN/OUT
Main power
a) These cords may only be used if their length does not exceed 2m between the point where the cord or cord guard enters
the appliance and the entry to the plug .
b) Cords having the cross-sectional areas indicated in the parentheses may be used for portable appliances if their length
does not exceed 2 m .
Grounding work
f
f
Grounding must be done by a qualified installer for your safety .
Grounding the power cable
f
f
The standard of grounding may vary according to the rated voltage and installation place of a heating pump .
f
f
Ground the power cable according to the following .
Installation place
Power condition
High humidity
Average humidity
Low humidity
Electrical potential of lower than 150V
Perform the grounding
work 3 .
Note 1)
Perform the grounding work 3 if
possible for your safety .
Note 1)
Electrical potential of higher than 150V
Must perform the grounding work 3 .
Note 1)
(In case of installing circuit breaker)
❋
❋
Note 1) Grounding work 3
• Grounding must be done by your installation specialist .
• Check if the grounding resistance is lower than 100 Ω .
When installing a circuit breaker that can cut the electric circuit in case of a short circuit, the allowable grounding
resistance can be 30~500 Ω .