Pipe work
Refrigerant pipe work
For all guide lines, specifications regarding refrigerant pipe work between the indoor unit and the outdoor unit, please follow
the outdoor unit installation manual .
Gas pipe (O .D .)
Liquid pipe (O .D .)
Indoor unit
15 .88 mm (5/8 inch)
6 .35 mm (1/4 inch)
Outdoor unit
15 .88 mm (5/8 inch)
6 .35 mm (1/4 inch)
Outer diameter [mm(inch)]
Torque (N•m)
ø6 .35 (1/4")
14~18
ø9 .52 (3/8")
34~42
ø12 .70 (1/2")
49~61
ø15 .88 (5/8")
68~82
ø19 .05 (3/4")
100~120
• When connecting the refrigerant pipes, always use 2 wrenches/spanners for tightening or loosening nuts . If not,
piping connections can be damaged .
CAUTION
Liquid pipe
Gas pipe