Power Cable Specifications
Single Phase
The power cable is not supplied with air conditioner.
-
Select the power supply cable in accordance with relevant local and national regulations.
-
Wire size must comply with the applicable local and national code.
-
Specifications for local wiring power cord and branch wiring are in compliance with local cord.
Type of
outdoor
unit
Model
Outdoor Units
Input Current [A]
Power Supply
Outdoor Unit
Indoor Unit
Rated
Voltage Range Outdoor (Down_Amp)
Indoor
Total
MCA
MFA
Hz
Volts
Min.
Max.
Cooling
Heating
A
AC160JXAFKH AC160JNHFKH 50
220-240
198
264
32
32
2 .5
34 .5
34 .5
40
3 Phase
Type of
outdoor
unit
Model
Outdoor Units
Input Current [A]
Power Supply
Outdoor Unit
Indoor Unit
Rated
Voltage Range
Outdoor (Down_Amp)
Indoor
Total
MCA
MFA
Hz
Volts
Min .
Max .
Cooling
Heating
A
AC160JXAFNH AC160JNHFKH 50
380-415
342
456 .5
16 .1
16 .1
2 .5
18 .6
18 .6
20 .46
AC180JXA
NH AC180JNH
KH 50
380-415
342
456 .5
16 .1
16 .1
2 .5
18 .6
18 .6
20 .46
B
AC200KXAPNH AC200KNHPKH 50
380-415
342
456 .5
-
-
-
-
25 .0
31 .25
AC250KXAPNH AC250KNHPKH 50
380-415
342
456 .5
-
-
-
-
25 .0
31 .25
1. Voltage range
- Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range
limits
2 . Maximum allowable voltage variation between phases is 2% .
3 . Wire size & type must comply with the applicable local and national code .
- Wire size : Based on the value of MCA .
- Wire type : 60245 IEC57(IEC) or H05RN-F(CENELEC) grade or more .
4 . MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker) .
5 . MCA represents maximum input current .
MFA represents capacity which may accept MCA
Abbreviations
- MCA : Min . Circuit Amps . (A)
- MFA : Max . Fuse Amps . (A)
6 . This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc(*2)
at the interface point between the user’s supply and the public system . It is the responsibility of the installer or user of
the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is
connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc(*2) .
[Ssc (*2)]
Model
Ssc[MVA]
AC160JXAFKH
2 .075
AC160JXAFNH
0 .725
AC180JXA
NH
2 .944
AC200KXAPNH
2 .459
AC250KXAPNH
4 .139