Samsung AC071TN4PKC Скачать руководство пользователя страница 9

9

English

Installation Pr

oc

edur

e

Perform the following steps to install inspection holes 
in accordance with the panel type.

For the recessed installation of the square panel.

•  Install an inspection hole to the direction of 

connection parts of the refrigerant pipe and the 
drain hose. (1 point)

Refrigerant pipe

Inspection hole

Indoor unit 

display

For recessed installation of the circular panel

•  Install inspection holes to both directions of the 

connection part of the refrigerant pipe and the 
drain hose and of the indoor unit display.  
(2 points)

Refrigerant pipe

Inspection hole

Indoor unit display

Inspection hole

Insert bolt anchors, use existing ceiling supports or 
construct a suitable support as shown in figure.

Concrete

Insert

Suspension bolt (M10) - eld supply

Hole in anchor

Hole in plug

Install the suspension bolts, depending on the ceiling 
type.

Ceiling support

  CAUTION

•  Make sure that the ceiling is strong enough to support 

the weight of the indoor unit. Before hanging the unit, 
test the strength of each attached suspension bolt.

•  If the length of the suspension bolt is more than 1.5 m, 

you are required to prevent vibration.

Screw eight pairs of nuts and washers to the 
suspension bolts, making space for hanging the indoor 
unit.

  CAUTION

•  You must install all of the suspension rods.
•  It is important to leave sufficient space in the false 

ceiling to allow access for maintenance or repairs to 
the drainage pipe connection, the refrigerant pipe 
connection, or to remove the unit if necessary.

Hang the indoor unit to the suspension bolts between 
two nuts. Cut a pad stopper and place it on the 
suspension bolts to hold the washers. Remove the 
stopper and screw the nuts to fix the unit.

1

2

2

Содержание AC071TN4PKC

Страница 1: ...Airconditioner Installation manual AC TN4PKC Thank you for purchasing this Samsung air conditioner Before operating this unit please read this manual carefully and retain it for future reference ...

Страница 2: ...t gas from the indoor unit 10 Step 6 Cutting and flaring the pipes 10 Step 7 Connecting the assembly pipes to the refrigerant pipes 11 Step 8 Performing the gas leak test 12 Step 9 Insulating the refrigerant pipes 12 Step10 Installing the drain hose and drain pipe 13 Step11 Performing the drainage test 15 Step12 Connecting the power and communication cables 15 Step13 Optional Extending the power c...

Страница 3: ...orlaundry Do not use the units if damaged If problems occur switch the unit off and disconnect it from the powersupply In orderto prevent electric shocks fires orinjuries always stop the unit disable the protection switch and contact SAMSUNG s technical support if the unit produces smoke if the powercable is hot ordamaged orif the unit is very noisy Always rememberto inspect the unit electric conn...

Страница 4: ... Verifythat the voltage and frequency of the powersupply complywith the specifications and that the installed power is sufficient to ensure the operation of any otherdomestic appliance connected to the same electric lines Always verifythat the cut off and protection switches are suitably dimensioned Verifythat the airconditioneris connected to the power supply in accordance with the instructions p...

Страница 5: ...d public access and is not touchable by users Rigid wall without vibration Where it is not exposed to direct sunshine Where the airfilter can be removed and cleaned easily Do not install the airconditionerin following places Place where there is mineral oil or arsenic acid Resin parts flame and the accessories may drop orwater may leak The capacity of the heat exchanger may reduce orthe air condit...

Страница 6: ...60 950 960 358 116 1050 883 Large Large 385 404 Refrigerant pipe Wire insert hole Drain hose connector 128 166 66 181 190 317 357 94 100 153 162 289 138 Small 385 66 166 128 181 190 233 404 Refrigerant pipe Drain hose connector Wire insert hole 94 138 100 153 162 205 Common 646 646 942 80 787 H1 ø100 ߣ ९ øɇθ ʪॐࡥ øɇθ ʪࡤ ߣߪߢࡥ Ɗ ɇ ࡤ ߣߧߢ ߤ ९ øɇθ ʪॐࡥ øɇθ ʪࡤ ߣߧߤࡥ Ɗ ɇ ࡤ ߣߤߤ H2 Square panel Circularpanel ...

Страница 7: ... be at least 450 mm x 450 mm A suspended ceiling structure can substitute forthe inspection holes Category Inspection hole Recessed installation Exposed installation Integrated suspended Square panel 1 ea Circularpanel 2 ea Forthe recessed installation of the circular panel Unit mm 1050 883 ø1010 to1020 Ceiling opening diameter ø1010 to1020 Inspection hole Indoorunit display Refrigerant pipe Inspe...

Страница 8: ... the indoor unit Cut away the part where pipes are pulled out forthe insulating work A Insulate the end of the pipe and some curved area by using separate insulator NOTE A Reference forthe outer circumference of the unit When insulating the body of the indoor unit use A as the reference for its outer circumference Unit mm Indoorunit type and models Dimensions 360 cassette type S 947 x 947 x 281 AC...

Страница 9: ...olt M10 eld supply Hole in anchor Hole in plug 4 Install the suspension bolts depending on the ceiling type Ceiling support CAUTION Make sure that the ceiling is strong enough to support the weight of the indoor unit Before hanging the unit test the strength of each attached suspension bolt If the length of the suspension bolt is more than1 5 m you are required to prevent vibration 5 Screw eight p...

Страница 10: ... refrigerant pipe Insulator Gas side Liquid side NOTE To prevent dirt orforeign objects from getting into the pipes during installation do not remove the pinch pipe completely until you are ready to connect the piping Step 6 Cutting and flaring the pipes 1 Make sure that you have the required tools available pipe cutter reamer flaring tool and pipe holder 2 If you wish to shorten the pipes cut the...

Страница 11: ... tube to protect the condensate water on the outside of the pipe falling onto the floor and to improve the efficiency of the unit 3 Cut off any excess foam insulation 4 Make sure that there are no cracks orwaves on the bent area 5 It would be necessary to double the insulation thickness 10 mm or more to prevent condensation even on the insulatorwhen if the installed area is warm and humid CAUTION ...

Страница 12: ...n tightlywithout any gaps 3 Finish wrapping insulating tape around the rest of the pipes leading to the outdoor unit 4 The pipes and electrical cables connecting the indoor unit with the outdoor unit must be fixed to the wall with suitable ducts CAUTION Make sure that all refrigerant connection must be accessible for easy maintenance and detachment Install the insulation not to get wider and use t...

Страница 13: ...e and cooling are not covered For example pipes installed at a corridor of a dormitory and studio or near an exit that opens and closes frequently Places where the pipes are installed that are highly humid due to a lack of ventilation Step10 Installing the drain hose and drain pipe 1 Push the supplied drain hose as far as possible over the drain socket 2 Tighten the metal clamp as shown in the pic...

Страница 14: ...terto flow backwards when the unit is stopped resulting in waterleaks Undergradient Ceiling Do not applyforce to the piping on the unit side when connecting the drain hose The hose should not be allowed to hang loose from its connection to the unit Fasten the hose to a wall frame orothersupport as close to the unit as possible Support pieces 1 to1 5 m 1 100 ormore Ceiling Install horizontally Be h...

Страница 15: ...the control box cover of the indoor unit Connect the power supply 220V 60 Hz to the L and N terminals Reassemble the control box cover and turn on the indoor unit CAUTION When the float switch is not detected due to insufficient water on the drain pan the drain pump will not work If the power supply is directly connected to the L and N terminals communication error message might appear After compl...

Страница 16: ...rough the ceiling the hole on the wall 4 Reassemble the electrical component box cover carefully tightening the screw 1 phase Indoorunit Outdoorunit Indoorpower Main powercable Communication cable Indoorpowersupply Powersupply Max Min V Indoorpowercable 220 to 240V 60 Hz 10 ߢ ߩߧ ࠌ ८ࡥ ߥ и θʪϑ Communication cable 0 75 mm 2 wires 9 8 7 5 19 0 13 8 12 6 9 0 Unit mm AC power M4 screw Communication M3 5...

Страница 17: ...traction tube 3 Insert both sides of core wire of the power cable into the connection sleeve Method1 Push the core wire into the sleeve from both sides Method 2 Twist the wire cores together and push it into the sleeve Method1 Connection sleeve Connection sleeve Method 2 CAUTION If cable wires are connected without using connecting sleeves theircontact area becomes reduced orcorrosion develops on ...

Страница 18: ... electric wire please DO NOT use a round shaped Pressing socket Incomplete wire connections can cause electric shock or a fire Step14 Settingtheindoorunit addressesandtheinstallationoptions If the indoorunit requires a high level controller you must set the indoorunit address But you must always set the installation options and set them by using the remote control You cannot set both of the indoor...

Страница 19: ...G22 SEG23 SEG24 3 X X X X X On SEG1 to SEG12 Off SEG13 to SEG24 Steps Remote control display 1 Set the SEG2 and SEG3 values a Set the SEG2 value by rotating the Wheel counterclockwise until the value you want to set appears on the remote control display SEG2 b Set the SEG3 value by rotating the Wheel clockwise until the value you want to set appears on the remote control display SEG3 When you rota...

Страница 20: ... the following order 6 Press the Mode button Fan and On appear on the remote control display 7 Set the SEG9 and SEG10 values a Set the SEG9 value by rotating the Wheel counterclockwise until the value you want to set appears on the remote control display SEG9 b Set the SEG10 value by rotating the Wheel clockwise until the value you want to set appears on the remote control display SEG10 When you r...

Страница 21: ... Set the SEG15 value by rotating the Wheel clockwise until the value you want to set appears on the remote control display SEG15 When you rotate the Wheel values appear in the following order 12 Press the Mode button Cool and Off appear on the remote control display 13 Set the SEG16 and SEG17 values a Set the SEG16 value by rotating the Wheel counterclockwise until the value you want to set appear...

Страница 22: ...t the SEG21 value by rotating the Wheel counterclockwise until the value you want to set appears on the remote control display SEG21 b Set the SEG22 value by rotating the Wheel clockwise until the value you want to set appears on the remote control display SEG22 When you rotate the Wheel values appear in the following order 18 Press the Mode button Heat and Off appear on the remote control display...

Страница 23: ...cordance with the option values you have set a Reset the indoor or outdoor unit Indoor unit Press the Set and Option buttons on the remote control simultaneously for 4 seconds Outdoor unit Press the K3 button b Remove the batteries from the remote control insert them again and then press the Power button on the remote control MR EC00 and MR EH00 remote controls Low Temp button High Temp button Mod...

Страница 24: ...ff SEG13 to SEG24 Take the steps presented in the following table Steps Remote control display 1 Set the SEG2 and SEG3 values a Set the SEG2 value by pressing the Low Fan button repeatedly until the value you want to set appears on the remote control display SEG2 b Set the SEG3 value by pressing the High Fan button repeatedly until the value you want to set appears on the remote control display Wh...

Страница 25: ...er SEG8 6 Press the Mode button Fan and On appear on the remote control display 7 Set the SEG9 and SEG10 values a Set the SEG9 value by pressing the Low Fan button repeatedly until the value you want to set appears on the remote control display SEG9 b Set the SEG10 value by pressing the High Fan button repeatedly until the value you want to set appears on the remote control display When you press ...

Страница 26: ...he remote control display SEG14 b Set the SEG15 value by pressing the High Fan button repeatedly until the value you want to set appears on the remote control display When you press the Low Fan or High Fan button values appear in the following order SEG15 12 Press the Mode button Cool and Off appear on the remote control display 13 Set the SEG16 and SEG17 values a Set the SEG16 value by pressing t...

Страница 27: ...splay When you press the Low Fan or High Fan button values appear in the following order SEG20 16 Press the Mode button Fan and Off appear on the remote control display 17 Set the SEG21 and SEG22 values a Set the SEG21 value by pressing the Low Fan button repeatedly until the value you want to set appears on the remote control display SEG21 b Set the SEG22 value by pressing the High Fan button rep...

Страница 28: ...the indoor unit and then press the Power button on the remote control twice Make sure that this command is received by the indoor unit When it is successfully received you can hear a short sound from the indoor unit If the command is not received press the Power button again 5 Check whetherthe air conditioner operates in accordance with the option values you have set a Reset the indoor or outdoor ...

Страница 29: ...Details Indication Details Indication Details Indication Details Indication Details 0 A 0 No main address 0 to1 Tens digit 0 to 9 Units digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Function Page Reserved Setting RMC address Reserved Group channel x16 Group address Indication and details Indication Details Indication Details Indication Details Indication Details 1 0 No ...

Страница 30: ...option Individual control with remote control allows you to control multiple indoor units individually by using the remote control Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Function Page Mode Reserved Use of external temperature sensor Use of central control Compensation of the fan RPM Indication and details Indication Details Indication Details Indication Details Indication Details Indication Details ...

Страница 31: ...ion SEG19 SEG20 SEG21 SEG22 Function Page Individual controlwith remote control Heating setting compensation Reserved Indication and details Indication Details Indication Details Indication Details 3 0 or1 Indoor1 0 Default 2 Indoor2 1 2 C 3 Indoor3 2 5 C 4 Indoor4 Option SEG23 SEG24 Function Setting the MDS Kit installation option Cycle time of Swing Indication and details Indication Details Indi...

Страница 32: ...omaticallywhen it detects motion Users should control to turn on the indoor unit with remote control etc Changing the addresses and options individually When you want to change the value of a specific option referto the following table and follow the steps in Common steps forsetting the addresses and options on page 18 Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Function Page Mode Option mode to change T...

Страница 33: ...Їϩͱ mode To set more detailed operation conditions forthe indoor unit 2 use the S net Pro Setting up the ETO Communication between indoorand outdoorunits F1 and F2 External contact interface module MIM B14 Main indoorunit Sub indoorunit Erroroutput port 1 2 Contact input port 5 6 1 Main indoor unit Disable the external contact control Default Connect the S net pro2 to F1 and F2 Enable the ETO func...

Страница 34: ...he entrance control settings the sub indoor unit decides the mode set temperature and fan speed when contact inputs are given Main indoorunit Enable of ETO Enable of external contact Errorport output X X N A X O Output due to an error O X Output by ETO entrance conditions temperature time erroroccurrence O O Output by ETO entrance conditions temperature time erroroccurrence ŵʪɇʒц ϩͱ ʀͱ ϩθͱ ϩ ʪ ɇ ʀ...

Страница 35: ... in the middle of location for installation 2 Put a pencil at the opposite side of the pivot point fixed in place 3 Rotate the papercompass on its pivot point to draw a line on the ceiling 4 Rotate the paper compass diametrically to draw a circle on the ceiling Forthe painting of the panel Make sure to only apply paints and varnishes for resins ABS HIPS or paint thinners If you apply lacquers for ...

Страница 36: ...the indoor temperature sensor X X X Error of the outdoor unit X X X Communication error between the indoor and outdoor units X X X Open or short circuit error of a sensor evaporator in evaporator out or discharge sensor in the indoor unit X X Error of the fan in the indoor unit X X Error of the second detection of the float switch X X Open circuit error of the thermal fuse X X EEPROM error X MDS M...

Страница 37: ...37 English Appendix Memo ...

Страница 38: ...38 English Appendix Memo ...

Страница 39: ...39 English Appendix ...

Страница 40: ...DB68 09104A 00 ...

Отзывы: