
17
English
Installation Pr
oc
edur
e
Step 13 Optional: Extending the
power cable
1
Prepare the following tools.
Tools
Spec
Shape
Crimping pliers
MH-14
Connection sleeve
(mm)
20xØ6.5
(HxOD)
Insulation tape
Width 19
mm
Contraction tube
(mm)
70xØ8.0
(LxOD)
2
As shown in the figure, peel off the shields from the
rubber and wire of the power cable.
• Peel off 20 mm of cable shields from the pre-
installed tube.
Power cable
(Unit: mm)
20
20
20
60
120
180
180
120
60
20
20
20
Pre-installed
tube for the
power cable
CAUTION
• For information about the power cable
specifications for indoor and outdoor units, refer to
the installation manual.
• After peeling off cable wires from the pre-installed
tube, insert a contraction tube.
3
Insert both sides of core wire of the power cable into
the connection sleeve.
•
Method 1
: Push the core wire into the sleeve from
both sides.
•
Method 2
: Twist the wire cores together and push it
into the sleeve.
Method 1
Connection sleeve
Connection sleeve
Method 2
CAUTION
• If cable wires are connected without using
connecting sleeves, their contact area becomes
reduced, or corrosion develops on the outer surfaces
of the wires (copper wires) over a long time. This may
cause an increase of resistance (reduction of passing
current) and consequently may result in a fire.
4
Using a crimping tool, compress the two points and flip it
over and compress another two points in the same location.
• The compression dimension should be 8.0.
Compression
dimension
• After compressing it, pull both sides of the wire to
make sure it is firmly pressed.
Method 1
Method 2
5 mm
Compress it 4 times.
Compress it 4 times.
5 mm
Содержание AC071TN4PKC
Страница 37: ...37 English Appendix Memo ...
Страница 38: ...38 English Appendix Memo ...
Страница 39: ...39 English Appendix ...
Страница 40: ...DB68 09104A 00 ...