Troubleshooting
Samsung Electronics
4-3
No.
Error Code
Meaning
Remarks
29
E396
DC voltage sensor error of Fan2
FAN2 error
30
E399
Heat sink temperature sensor error of Fan2
FAN2 error
31
E403
Compressor down due to freeze protection control
Check Outdoor Cond.
32
E404
System stop due to overload protection control
Check Comp. when it start
33
E416
System stop due to discharge temperature
-
34
E422
Blockage detected on high pressure pipe
1. Check if the service valve is open
2. Check for refrigerant leakage(pipe connections,
heat exchanger) and charge refrigerant if
necessary
3. Check if there's any blockage on refrigerant
cycle(indoor unit/outdoor unit)
4. Check if additional refrigerant has been added
after pipe extension
35
E425
Reverse phase or open phase
Check whether 3 phase is reversed or opened.
36
E440
Heating mode restriction due to high air temperature
HEATING
37
E441
Cooling mode restriction due to low air temperature
COOLING
38
E446
Error due to operation failure of Fan1
FAN1 error
39
E447
Motor wire of Fan1 is not connected
FAN1 error
40
E448
Lock error on Fan1 of outdoor unit
FAN1 error
41
E452
Error due to ZCP detection circuit problem or power failure
-
42
E453
Error due to overheated motor of outdoor unit's Fan1
FAN1 error
43
E455
Error due to overheated IPM of Fan1
FAN1 error
44
E458
Fan speed error
FAN1 ERROR
45
E461
Error due to operation failure of inverter compressor
-
46
E462
System stop due to full current control
-
47
E463
Over current trip / PFC over current error
Check OLP sensor
48
E464
IPM Over Current(O.C)
IPM
49
E465
Comp. Over load error
-
50
E466
DC-Link voltage under/over error
Check AC Power and DC Link Voltage
51
E467
Error due to abnormal rotation of the compressor or unconnected
wire of compressor
Check Comp wire
52
E468
Error on current sensor (Short or Open)
Check Outdoor Inverter PBA.
53
E469
Error on DC-Link voltage sensor (Short or Open)
-
54
E471
Outdoor EEPROM checksum error between MAIN and INVERTER
(AC
777
KXAPNH)
Check Outdoor EEPROM PBA
55
E472
AC Line Zero Cross Signal out
-
56
E473
Comp Lock error
-
57
E474
Error on IPM Heat Sink sensor of inverter 1 (Short or Open)
heck Outdoor Inverter PBA
58
E475
Error on inverter fan 2
FAN2 ERROR
59
E478
Error due to overcurrent of Fan1
FAN1 error
60
E484
PFC Overload (Over current) Error
Check Outdoor Inverter PBA.
61
E485
Error on input current sensor of inverter 1 (Short or Open)
Check Outdoor EEPROM PBA
62
E486
Over-voltage/low-voltage error of Fan1
FAN1 error