Troubleshooting
4-2
Samsung Electronics
4-2 Outdoor Trouble shooting
The table below give indication about self diagnostic routine. Some of error code requires activities exclusively
for Authorized Service Center.
Outdoor unit
If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and
INVERTER PCB.
No.
Error Code
Meaning
Remarks
1
E108
Error due to repeated address setting(when 2 or more devices has
same address within the network)
Check on repeated indoor unit main address
2
E121
Error on indoor temperature sensor of indoor unit(Short or Open)
Indoor unit Room Thermistor Open/Short
3
E122
Error on EVA IN sensor of indoor unit(Short or Open)
Indoor unit EVA_IN Thermistor Open/Short
4
E123
Error on EVA OUT sensor of indoor unit(Short or Open)
Indoor unit EVA_OUT Thermistor Open/Short
5
E153
Error on float switch (2nd detection)
"Indoor unit Float Switch Open/Short Drain Pump
operation Check"
6
E154
RPM feedback error of indoor unit
Check on indoor unit indoor Fan operation
7
E162
Outdoor unit EEPROM Read/Write error (H/W)
Check Outdoor EEPROM PBA
8
E163
Outdoor unit EEPROM Read/Write error (Option)
Check Outdoor EEPROM Data
9
E198
Error on thermal fuse of indoor unit (Open)
Thermal Fuse Open Check of indoor unit Terminal
Block
10
E201
"Communication error between indoor and outdoor
unit(Installation number setting error repeated
indoor unit address,indoor unit communication cable error)"
Check indoor quantity setting in outdoor
11
E202
"Communication error between indoor and outdoor
unit(Communication error on all indoor unit,
outdoor unit communication cable error)"
Check electrical connection and setting between
indoor unit and outdoor unit
12
E205
Communication error on all PBA within the outdoor unit
C-Box,communication cable error
-
13
E206
E206-C002 : Fan PBA communication error, E206-C003 : INV PBA
communication error
-
14
E221
Error on outdoor temperature sensor (Short or Open)
Check Outdoor sensor Open / Short
15
E231
Error on outdoor COND OUT sensor (Short or Open)
Check Cond-Out sensor Open / Short
16
E251
Error on discharge temperature sensor of compressor 1 (Short or
Open)
Check Discharge sensor Open / Short
17
E320
Error on OLP sensor (Short or Open)
Check OLP sensor Open / Short
18
E346
Error due to operation failure of Fan2
FAN2 error
19
E347
Motor wire of Fan2 is not connected
FAN2 error
20
E348
Lock error on Fan2 of outdoor unit
FAN2 error
21
E353
Error due to overheated motor of outdoor unit's Fan2
FAN2 error
22
E355
Error due to overheated IPM of Fan2
FAN2 error
23
E378
Error due to overcurrent of Fan2
FAN2 error
24
E386
Over-voltage/low-voltage error of Fan2
FAN2 error
25
E387
Hall IC connection error of Fan2
FAN2 error
26
E389
V-limit error on Fan2 of compressor
FAN2 error
27
E391
Error due to DataFlash of Fan2
FAN2 error
28
E393
Output current sensor error of Fan2
FAN2 error