Checking correct grounding

If the power distribution circuit does not have a grounding or the grounding does not comply with specifications, an 
grounding electrode must be installed. The corresponding accessories are not supplied with the air conditioner.

1.  Select an grounding electrode that complies with the specifications given in 

the illustration.

2.  Connect the flexible hose to the flexible hose port. 

f

In damp hard soil rather than loose sandy or gravel soil that has a higher 
grounding resistance.

f

Away from underground structures or facilities, such as gas pipes, water 
pipes, telephone lines and underground cables.

f

At least two meter away from a lightening conductor grounding electrode 
and its cable.

•  The grounding wire for the telephone line cannot be used to 

ground the air conditioner.

NOTE

3.  Finish wrapping insulating tape around the rest of the pipes leading to the 

outdoor unit.

Terminal M4

PVC-insulated green/ 

yellow wire

To grounding 

screw

Steel core

Carbon 

plastic

1.6 ft

1 ft

4.  Install a green/yellow coloured grounding wire :

f

If the grounding wire is too short, connect an extension lead, in a mechanical way and wrapping it with insulating tape 
(do not bury the connection).

f

Secure the grounding wire in position with staples.

•  If the grounding electrode is installed in an area of heavy traffic, its wire must be connected securely.

NOTE

5.  Carefully check the installation, by measuring the grounding resistance with a ground resistance tester. If the resistance is 

above required level, drive the electrode deeper into the ground or increase the number of grounding electrodes.

6.  Connect the grounding wire to the electrical component box inside of the outdoor unit.

Содержание AC030MXSCCC

Страница 1: ...conditioner Installation manual AC030MXSCCC AC036MXSCCC Thank you for purchasing this Samsung air conditioner Before operating this unit please read this manual carefully and retain it forfuture reference ...

Страница 2: ... stop valve 28 Interface module Installation Optional 29 Pump down Procedure 30 Checking correct grounding 31 Testing operations 32 Installing the wind baffle 35 OTHERS Troubleshooting 36 IMPORTANT This product has been designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropriate coil components However proper refrigerant charge and proper air flow are...

Страница 3: ...ch it has been designed the indoor unit is not suitable to be installed in areas used for laundry f Do not use the units if damaged If problems occur switch the unit off and disconnect it from the power supply f In order to prevent electric shocks fires or injuries always stop the unit disable the protection switch and contact SAMSUNG s technical support if the unit produces smoke if the power cab...

Страница 4: ...g operation of air conditioner in the condition where ambient temperature is lower than 23 F DB Dry bulb a wind baffle should be installed to protect the compressor of the outdoor unit Power supply line fuse or circuit breaker f Always make sure that the power supply is compliant with current safety standards Always install the air conditioner in compliance with current local safety standards f Al...

Страница 5: ...mage or scratches insert a piece of cloth between the outdoor unit and rope then move the unit The appearance of the unit may be different from the picture depending on the model Plate protection cloth Wire rope When moving an outdoor unit by hand f Moving the outdoor unit by lifting up and carrying due to the short travel distance Two people should carry the outdoor unit Be careful not to damage ...

Страница 6: ... open area f Maintain sufficient clearance around the outdoor unit especially from a radio computer stereo system etc Fuse Outdoor Unit Stereo 5ftormore Indoor Unit Control Air Guide Duct This product is not provided by Samsung 3 3 ft or more 3 3 ft o r m o re 5 ft or m or e 5ftormore 5 ft or more Fuse 8 inch 12 inch f If the outdoor unit is installed at a height ensure that its base is firmly fix...

Страница 7: ...ight and the width of the wall should be 1 5 times larger than the size of the outdoor unit Also secure over 27 6 inch between the protection wall and the outdoor unit for exhausted air to ventilate Protection wall Outdoor unit Sea breeze Sea Install the outdoor unit in a place where water can drain smoothly If you cannot find a place satisfying above conditions please contact manufacturer Make su...

Страница 8: ... is towards the wall 11 81 or more 5 91 or more 23 62 or more 59 06 or more 78 74 or more When 3 sides of the outdoor unit are blocked by a wall The upper part of the outdoor unit and the air outlet is towards the wall 19 69 or more 11 81 or more 11 81 or more 59 06 or more The upper part of the outdoor unit and the air outlet is opposite the wall When front and rear side of the outdoor unit is to...

Страница 9: ...owards the wall 11 81 or more 5 91 or more 23 62 or more 59 06 or more 78 74 or more When 3 sides of the outdoor unit are blocked by a wall The upper part of the outdoor unit and the air outlet is towards the wall 19 69 or more 11 81 or more 11 81 or more 59 06 or more The upper part of the outdoor unit and the air outlet is opposite the wall When front and rear side of the outdoor unit is towards...

Страница 10: ... 59 06 or more 23 62 or more 23 62 or more When front and rear side of the outdoor unit is towards a wall 59 06 or more 23 62 or more 118 11 or more 7 87 or more 118 11 or more When 3 sides of the outdoor unit are blocked by a wall The units must be installed according to the distances specified above in order to permit accessibility from each side to guarantee correct operation and for future mai...

Страница 11: ... unit are blocked by a wall 11 81 or more 59 06 or more 23 62ormore 23 62ormore When front and rear side of the outdoor unit is towards a wall 59 06 or more 23 62 or more 118 11 or more 7 87 or more 118 11 or more When 3 sides of the outdoor unit are blocked by a wall Should adopt bar type louver Don t use a type of rain resistance louver Bar type louver Rain resistance louver Louver specification...

Страница 12: ... ground Fix the outdoor unit with anchor bolts The anchor bolt must be 0 79 inch or higher from the base surface NOTE Unit inch Anchor bolt hole 13 0 14 2 15 1 24 4 37 0 Make a drain outlet around the base for outdoor unit drainage If the outdoor unit is installed on the roof you have to check the ceiling strength and waterproof the unit CAUTION Location of the compressor Make sure that product is...

Страница 13: ...be able to support the weight of rack and outdoor unit f Install the rack close to the column as much as possible f Install proper grommet in order to reduce noise and residual vibration transferred by outdoor unit towards wall When installing air guide duct Check and make sure that screws do not damage the copper pipe Secure air guide duct on guard fan CAUTION Soft rubber designed to cut off vibr...

Страница 14: ...aint around the hole f Secure the cable tube to the outdoor knockout using the CD connector and bushing During unit installation make refrigerant connections first then electrical connections If removing the unit disconnect electrical cables first then refrigerant connections Connect the air conditioner to grounding system before performing the electrical connection When installing the unit you sh...

Страница 15: ... 5 1 51 0 9 24 30 Between Indoor unit and Outdoor unit Connection Cable Specifications Common in use Power supply Communication Cable Power supply Max Min V Indoor Power Cable 1Φ 208 230V 60Hz 10 0 0039 in 3wires 0 0011 0 0023 in 2wires f Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord Code designation IEC 60245 IEC 57 CENE...

Страница 16: ...atly it may shorten the life of the condenser If the unbalanced power is exceeded over 4 of supply rating the indoor unit is protected stopped and the error mode indicates To protect the product from water and possible shock you should keep the power cable and the connection cord of the indoor and outdoor units within ducts with appropriate IP rating and material selection for your application Ens...

Страница 17: ...wer cable Cable clamp Outdoor Unit Indoor Power Communication cable Cable tie L F2 V2 F4 F1 V1 F3 N Lay the electrical wiring so that the front cover does not rise up when doing wiring work and attach the front cover securely Ground wire for the indoor unit and outdoor unit connection cable must be clamped to a soft copper tin plated eyelet terminal with M4 screw hole NOT SUPPLIEDWITH UNIT ACCESSO...

Страница 18: ...3 3 1 2 0 5 0 019 0 2 0 007 9 4 3 8 0 2 0 007 12 5 1 2 13 1 2 38 1 1 2 8 4 1 3 16 0 4 0 015 0 0 1 8 0 07 8 3 16 22 7 8 13 1 2 43 1 11 16 8 4 1 3 16 50 0 07 8 3 16 22 7 8 0 3 0 011 13 5 1 2 0 5 0 019 0 2 0 007 11 4 7 16 0 3 0 011 17 5 11 16 14 9 16 50 2 8 4 1 3 16 0 4 0 015 0 0 1 8 0 07 70 0 10 8 3 16 24 1 0 4 0 015 17 5 11 16 0 5 0 019 0 4 0 015 13 3 1 2 0 4 0 015 18 5 3 4 20 3 4 51 2 8 4 1 3 16 0...

Страница 19: ...he pre installed tube insert a contraction tube Unit mm 120 60 20 20 20 180 Power cable 20 Pre installed tube for the power cable 3 Insert both sides of core wire of the power cable into the connection sleeve f Method 1 Push the core wire into the sleeve from both sides Connection sleeve f Method 2 Twist the wire cores together and push it into the sleeve Connection sleeve 4 Using a crimping tool ...

Страница 20: ...be contraction work is completed wrap it with the insulation tape to finish Insulation tape Make sure that the connection parts are not exposed to outside Be sure to use insulation tape and a contraction tube made of approved reinforced insulating materials that have the same level of withstand voltage with the power cable Comply with the local regulations on extensions In case of extending the el...

Страница 21: ...h Minimum thickness inch Temper grade 1 4 0 0276 C1220T O 3 8 0 0276 1 2 0 0315 5 8 0 0394 5 8 0 0315 C1220T 1 2H OR C1220T H 3 4 0 0354 7 8 0 0354 Make sure to use C1220T 1 2H Semi hard pipe for more than 3 4 in In case of using C1220T O Soft pipe for 3 4 in pipe may be broken which can result in an injury CAUTION Make at least one round It will reduce noise and vibration The appearance of the un...

Страница 22: ...th liquid stop valve and gas stop valve 2 Operate the air conditioner by pressing the K2 key on the outdoor unit PCB 3 About 30 minutes later charge the refrigerant through the service port of gas stop valve If necessary refer to the pressure table classified by outdoor temperature NOTE 1 Ref Gas side stop valve service port Outdoor unit Indoor unit Balance Vacuum pump Liquid side stop valve servi...

Страница 23: ...e right figure 1 Connect each assembly pipe to the appropriate valve on the outdoor unit and tighten the flare nut 2 Referring to the illustration opposite tighten the flare nut on section B first manually and then with a torque wrench applying the following torque Outer Diameter D Torque lbf ft ø6 35 mm 1 4 10 3 13 3 ø9 52 mm 3 8 25 0 31 0 ø12 70 mm 1 2 36 1 45 0 ø15 88 mm 5 8 50 2 60 5 ø19 05 mm...

Страница 24: ...e of 158 8 lbf in with a torque wrench 8 Check for gas leakage f At this time especially check for gas leakage from the 3 way valve s stem nuts A port and from the service port cap B liquid A gas Connect the indoor and outdoor units using pipes with flared connections not supplied For the lines use insulated unwelded degreased and deoxidized copper pipe Cu DHP type to ISO 1337 or UNI EN 12735 1 su...

Страница 25: ...onnect the drain hose to the drain plug 4 Ensure that the drained water runs off correctly and safely 3 2 inch 0 51 inch 5 Be sure to plug the rest of drain holes not connected with drain plugs using drain caps DRAIN CAP 3EA DRAIN PLUG 1EA When installing the product make sure that the rack is not placed under the drain hole If the product is installed in a region of heavy snow allow enough separa...

Страница 26: ...34 0 36 ø12 70 mm 1 2 0 079inch 12 8 13 2 0 50 0 52 ø15 88 mm 5 8 0 087inch 16 2 16 6 0 64 0 65 ø19 05 mm 3 4 0 087inch 19 3 19 7 0 76 0 78 5 Check that the flaring is correct referring to the illustrations below for examples of incorrect flaring Uneven Thickness Cracked Damaged Surface Inclined Correct 6 Align the pipes and tighten the flare nuts first manually and then with a torque wrench apply...

Страница 27: ...r Refrigerant pipe work Once you have checked that there are no leaks in the system you can insulate the piping and hose 1 To avoid condensation problems place an insulator around each refrigerant pipe When insulate the pipe be sure to overlap the insulation NOTE When insulating the pipe use non slit insulator CAUTION NBR 2 Select the insulation of the refrigerant pipe f Insulate the gas side and ...

Страница 28: ...lve 1 Open the cap and turn the stop valve counterclockwise by using a hexagonal wrench 2 Turn it until the axis is stopped Do not apply excessive force to the stop valve and always use special instruments Otherwise the stopping box can be damaged and the back sheet can leaks If the watertight sheet leaks turn the axis back by half tighten the stopping box then check the leakage again If there is ...

Страница 29: ...See the picture 2 Attach the Interface module PCB to the case in the control box in the outdoor unit then connect the power and the communication cable between the Interface module and the outdoor unit refer to the figure of pages 16 17 3 If you install a Interface module to an outdoor unit every indoor unit which is connected to an outdoor unit can be controlled simultaneously 4 Each outdoor unit...

Страница 30: ... the low pressure side 5 Stop operation of the air conditioner by pressing the Power button on the indoor unit or remote control 6 Cut the power at the circuit breaker and then disconnect the pipes B liquid A gas A Low pressure side B High pressure side Relocation of the air conditioner Refer to this procedure when the unit is relocated Carry out the pump down procedure refer to the details of pum...

Страница 31: ...the telephone line cannot be used to ground the air conditioner NOTE 3 Finish wrapping insulating tape around the rest of the pipes leading to the outdoor unit Terminal M4 PVC insulated green yellow wire To grounding screw Steel core Carbon plastic 1 6 ft 1 ft 4 Install a green yellow coloured grounding wire f If the grounding wire is too short connect an extension lead in a mechanical way and wra...

Страница 32: ...nected correctly 3 KEY buttons are on Main PBA of Outdoor Unit 3 Press K2 on the outdoor unit PCB to run the test mode and stop K2 Mode DISPLAY 1 CoolingTest Mode 2 Inverter checker Load PBA inspection operation 3 Pump down in Cool mode 4 After 12 minutes of stationary condition check each indoor unit air treatment f Cooling mode indoor unit check Inlet air temp Outlet air temp 18 F reference only...

Страница 33: ...ty sum of indoor units C Tens digit Unit digit The first place of decimals kW 13 Protective control D 0 Cooling 1 Heating Protective control 0 No Protective control 1 Freezing 2 Non stop defrosting 3 Over load 4 Discharge 5 Total electric current Frequency status 0 Normal 1 Hold 2 Down 3 Up_limit 4 Down_limit 14 The temperature of heat radiating plate E Hundreds digit Tens digit Unit digit 15 S W ...

Страница 34: ...de is in use eco mode standby mode will not be functional For AC030 36MXSCCC model Snow prevention mode is set as default f DIP switch SW508 option On default Off Switch 1 Auto Silence Mode Manual Silence Mode Switch 2 Switch 3 Switch 4 8 Silence Mode DIP switch option f DIP switch SW507 option Switch 3 Switch 4 Operation On On Disable Silence mode On Off Silence mode 1st step Off On Silence mode ...

Страница 35: ... reverse way Wind baffle is not supplied with the product Make holes on both sides and attach the wind baffle using screws Make holes on both sides and attach the wind baffle using screws 24 6 inch 0 63 inch Partition FrontView A A Top DownView A Should be 7 7 8 inch or longer When attaching the wind baffle using screws be careful that the screws do not damage the partition and the heat exchanger ...

Страница 36: ...r is supplied The error occurs regardless of the number of units Check indoor quantity setting in outdoor 9 E202 Communication error between indoor unit and outdoor unit When there is no response from indoor units after tracking is completed Check electrical connection and setting between indoor unit and outdoor unit 10 E203 Communication error between outdoor unit inv main micom For PF 4 6 contro...

Страница 37: ...rrent sensor Short or Open Check Outdoor Inverter PBA 31 E469 Error on DC Link voltage sensor Short or Open 32 E470 Outdoor unit EEPROM Read Write error Option Check Outdoor EEPROM Data 33 E471 Outdoor unit EEPROM Read Write error H W Check Outdoor EEPROM PBA 34 E472 AC Line Zero Cross Signal out 35 E473 Comp Lock error 36 E474 Error on IPM Heat Sink sensor of inverter 1 Short or Open Check Outdoo...