When installing more than 1 outdoor unit (with wind baffle)
f
Wind baffle is not supplied with the product.
(Unit : inch)
59.06 or mor
e
❋
When the air outlet is towards a wall
11.81 or mor
e
11.81 or more
23.62 or more
23.62 or more
23.62 or more
❋
When 3 sides of the outdoor unit are blocked by a wall
11.81 or
mor
e
59.06 or mor
e
23.62 or more
23.62 or more
❋
When front and rear side of the outdoor unit is towards a wall
59.06 or more
23.62 or more
118.11 or more
7.87 or more
118.11 or more
❋
When 3 sides of the outdoor unit are blocked by a wall
• Should adopt bar type louver. Don’t use a type of rain resistance louver.
[Bar type louver]
[Rain resistance louver]
• Louver specifications.
- Angle criteria : less than 20˚
- Opening ratio criteria : greater than 80%