19
Ins
tallation Pr
oc
edur
e
English
1 phase (AC036/048TNMPEH)
Cable clamp
L N
F1 F2
Indoor Unit
Indoor power cable
Main power cable
Communication
cable
Cable tie
1(L)
2(N)
L
N
F1
F2
Outdoor Unit
3 phase (AC060TNMPEH)
1(L)
2(N)
L1(R)
L2(S)
L3(T)
N
F1
F2
Indoorpower cable
Main power cable
Communication
cable
Cable tie
Outdoor Unit
Indoor Unit
Cable clamp
1(L)
2(N)
1
2
V1
V2
F3
F4
F2
F1
Indoor power supply
Power supply
Max/Min(V)
Indoor power cable
1ø,220 to 240 V,50 Hz
±10%
1.5 mm², 3 wires
Communication cable
0.75 mm², 2 wires
11
13
7.5
9.0
18
13.8
AC power: M4 screw
Communication: M3.5 screw
Tightening torque (kgf • cm)
M3.5
8.0 to 12.0
M4
12.0 to 18.0
• 1 N·m = 10 kgf·cm
• Power supply cords of parts of appliances for
outdoor use shall not be lighter than polychloroprene
sheathed flexible cord.
– Code designation
∙
[1-phase]
IEC: 60245 IEC 57 / CENELEC: H05RN-F
grade or more
∙
[3-phase]
IEC: 60245 IEC 66 / CENELEC: H07RN-F
grade or more
• Since it has the external power supply, refer to the
outdoor unit installation manual for MAIN POWER.
CAUTION
• When installing the indoor unit in a computer
room or a server room, use the double shielded
communication cable (tape aluminum / polyester
braid + copper) of FROHH2R type.
Содержание AC TNMPEH Series
Страница 34: ......