17
Ins
tallation Pr
oc
edur
e
English
1~1.5m
Horizontal drainpipe
more than 1/100 slope
Ceiling
Hanger
Flexible hose
With the drain pump
1
The drain pipe should be installed within 300mm to
550mm from the flexible hose and then lift down 20mm
or more.
2
Install horizontal drainpipe with a slope of 1/100 or
more and fix it by hanger space of 1.0~1.5m.
3
Install the air vent in the horizontal drainpipe to prevent
water flow back to the indoor unit.
NOTE
• You may not need to install it if there were proper
slope in the horizontal drainpipe.
4
The flexible hose should not be installed upward
position, it may cause water flow back to the indoor unit.
1~1.5m
20mm
or more
200mm
or more
Hanger
Within
300~550mm
Air vent
300mm or less
Flexible hose
Horizontal drainpipe
more than 1/100 slope
Ceiling
Step 11 Performing the drainage test
Prepare a little water about 2 liter.
1
Pour water into the base pan in the indoor unit as shown
in figure.
2
Confirm that the water flows out through the drain hose.
AC018/024/036/048TNMPEH
AC060TNMPEH
Step 12 Optional: Installing external
controller&Ionizer
Accessories (External controller : MIM-B14)
External Controller
PCB Case
Haness Wire
Haness Wire
Screw