14
Installation Procedure
English
Ins
tallation Pr
oc
edur
e
Indoor power supply
Power supply
Max/
Min(V)
Indoor power cable
220 to 240 V, 50/60 Hz
±10%
0.75 to 1.5 mm², 3 wires
Communication cable
0.75 to 1.5 mm², 2 wires
AC power: M4 screw
Communication: M3.5 screw
10.3
13.8
10.1
11.4
19.2
19.2
Tightening torque (kgf • cm)
M3.5
8.0 to 12.0
M4
12.0 to 18.0
• 1 N·m = 10 kgf·cm
• Power supply cords of parts of appliances for outdoor
use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 57 /
CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC:
H07RN-F)
• Since it has the external power supply, refer to the
outdoor unit installation manual for MAIN POWER.
CAUTION
• When installing the indoor unit in a computer room or
a server room, use the double shielded communication
cable (tape aluminum / polyester braid + copper) of
FROHH2R type.
Step 12 Optional: Extending the
power cable
1
Prepare the following tools.
Tools
Spec
Shape
Crimping pliers
MH-14
Connection sleeve
(mm)
20xØ6.5
(HxOD)
Insulation tape
Width 19
mm
Contraction tube
(mm)
70xØ8.0
(LxOD)
2
As shown in the figure, peel off the shields from the
rubber and wire of the power cable.
• Peel off 20 mm of cable shields from the pre-
installed tube.
CAUTION
• For information about the power cable specifications
for indoor and outdoor units, refer to the installation
manual.
• After peeling off cable wires from the pre-installed
tube, insert a contraction tube.
• If cable wires are connected without using connecting
sleeves, their contact area becomes reduced, or
corrosion develops on the outer surfaces of the wires
(copper wires) over a long time. This may cause an
increase of resistance(reduction of passing current)
and consequently may result in a fire.
Power cable
(Unit: mm)
20
20
20
60
120
180
20
20
20
60
120
180
Pre-installed
tube for the
power cable