Installation Procedure

Installation Pr

oc

edur

e

English

•  Since it has the external power supply, refer to the 

outdoor unit installation manual for MAIN POWER.

  CAUTION

•  When installing  the indoor unit in a computer 

room or network room, use the double shielded 
communication cable (tape aluminum / polyester 
braid + copper) of FROHH2R type.

•  Select the power cable in accordance with relevant 

local and national.

•  Wire size must comply with local and national code.
•  You should connect the power cable into the power 

cable terminal and fasten it with a clamp.

•  The unbalanced power must be maintained within 10% 

of supply rating among whole indoor units.

•  If the power is unbalanced greatly, it may shorten 

the life of the condenser. If the unbalanced power is 
exceeded over 10% of supply rating, the indoor unit is 
protected, stopped and the error mode indicates

•  Connect the power cable to the auxiliary circuit 

breaker. An all pole disconnection from the power 
supply must be incorporated in the fixed wiring 

࣑क़ߥ͔͔࣒࢏

•  You must keep the cable in a protection tube.
•  Maximum length of power cables are decided within 

10% of power drop. If it exceeds, you must consider 
another power supplying method.

•  The circuit breaker (MCCB, ELB) should be considered 

more capacity if many indoor units are connected from 
one breaker.

•  Use round pressure terminal for connections to the 

power terminal block.

•  For wiring, use the designated power cable and 

connect it firmly, then secure to prevent outside 
pressure being exerted on the terminal board.

•  Use an appropriate screwdriver for tightening the 

terminal screws. A screwdriver with a small head will 
strip the head and make proper tightening impossible.

•  Over-tightening the terminal screws may break them.

Step 13  Optional: Extending the power 

cable

Prepare the following tools.

Tools

Spec

Shape

Crimping pliers

MH-14

Connection sleeve 

(mm)

20xØ6.5 

(HxOD)

Insulation tape

Width 19 

mm

Contraction tube 

(mm)

70xØ8.0 

(LxOD)

As shown in the figure, peel off the shields from the 
rubber and wire of the power cable.
•  Peel off 20 mm of cable shields from the pre-

installed tube.

  CAUTION

•  For information about the power cable 

specifications for indoor and outdoor units, refer to 
the installation manual.

•  After peeling off cable wires from the pre-installed 

tube, insert a contraction tube.

Power cable

Pre-installed tube for the power cable

(Unit: mm)

(Unit: mm)

20

20

20

20

60

120

180

Содержание AC NN4DKH Series

Страница 1: ...Airconditioner Installation manual AC NN4DKH Thank you for purchasing this Samsung air conditioner Before operating this unit please read this manual carefully and retain it for future reference...

Страница 2: ...rging inert gas from the indoor unit Step 6 Cutting and flaring the pipes Step 7 Connecting the assembly pipes to the refrigerant pipes Step 8 Performing the gas leak test Step 9 Insulating the refrig...

Страница 3: ...designed the indoor unit is not suitable to be installed in areas used for laundry Do not use the units if damaged If problems occur switch the unit off and disconnect it from the powersupply In orde...

Страница 4: ...c lines Always verify that the cut off and protection switches are suitably dimensioned Verify that the airconditioneris connected to the power supply in accordance with the instructions provided in t...

Страница 5: ...whetherthe chosen location is well drained The indoor unit must be installed such that it is beyond public access and is not touchable by users Do not install the airconditionerin following places Pl...

Страница 6: ...uspension bolts 950 71 60 41 Model AC052NN4DKH AC071NN4DKH AC090NN4DKH AC100NN4DKH AC120NN4DKH AC140NN4DKH Chassis Small Large Large A 215 238 B 105 127 C 196 222 Net dimension W D H mm 840 X 840 X 20...

Страница 7: ...and carry the indoor unit Step 3 Optional Insulating the bodyof the indoorunit If you install a cassette type indoor unit on the ceiling when temperature is over 27 C and humidity is over 80 you must...

Страница 8: ...the length of the suspension bolt is more than1 5 m you are required to prevent vibration 4 Screw eight pairs of nuts and washers to the suspension bolts making space for hanging the indoor unit CAUT...

Страница 9: ...If you wish to shorten the pipes cut them with a pipe cutter ensuring that the cut edge remains at a 90 angle to the side of the pipe Referto the illustrations below for examples of edges cut correctl...

Страница 10: ...ate water on the outside of the pipe falling onto the floor and to improve the efficiency of the unit 3 Cut off any excess foam insulation 4 Make sure that there are no cracks orwaves on the bent area...

Страница 11: ...tion tightlywithout any gaps 3 Finish wrapping insulating tape around the rest of the pipes leading to the outdoor unit 4 The pipes and electrical cables connecting the indoor unit with the outdoor un...

Страница 12: ...dormitory and studio or near an exit that opens and closes frequently Places where the pipes are installed that are highly humid due to a lack of ventilation Step10 Installing the drain hose and drai...

Страница 13: ...ks Under gradient Ceiling Do not apply force to the piping on the unit side when connecting the drain hose The hose should not be allowed to hang loose from its connection to the unit Fasten the hose...

Страница 14: ...nly in the Cool mode you can check the correct operation of the drain pump When the electric cable connection has not been completed Remove the control box cover of the indoor unit Connect the power s...

Страница 15: ...the side of the indoor unit and connect the cable to the terminals referto the figure below 3 Route the other end of the cable to the outdoor unit through the ceiling the hole on the wall 4 Reassemble...

Страница 16: ...within 10 of power drop If it exceeds you must consider another power supplying method The circuit breaker MCCB ELB should be considered more capacity if many indoor units are connected from one break...

Страница 17: ...th the insulation tape twice or more and position your contraction tube in the middle of the insulation tape Three or more layers of insulation are required Method 1 Method 2 Insulation tape 35 mm 40...

Страница 18: ...High Temp and Low Temp buttons simultaneously insert the batteries into the remote control c Make sure that you are entered to the mode for setting the options 2 Set the option values CAUTION The tota...

Страница 19: ...e SEG4 value by pressing the Low Fan button repeatedly until the value you want to set appears on the remote control display SEG4 b Set the SEG5 value by pressing the High Fan button repeatedly until...

Страница 20: ...ontrol display When you press the Low Fan or High Fan button values appear in the following order SEG10 8 Press the Mode button Heat and On appear on the remote control display 9 Set the SEG11 and SEG...

Страница 21: ...the Low Fan button repeatedly until the value you want to set appears on the remote control display SEG16 b Set the SEG17 value by pressing the High Fan button repeatedly until the value you want to...

Страница 22: ...you want to set appears on the remote control display When you press the Low Fan or High Fan button values appear in the following order SEG22 18 Press the Mode button Heat and Off appear on the remot...

Страница 23: ...the remote control twice Make sure that this command is received by the indoor unit When it is successfully received you can hear a short sound from the indoor unit If the command is not received pres...

Страница 24: ...on or off controller set RMC address Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Function Page Mode Setting main address Reserved Indoorunit number Indoorunit number Indication and details Indication Detail...

Страница 25: ...h remote control allows you to control multiple indoor units individually by using the remote control Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Function Page Mode Reserved Use of external temperature senso...

Страница 26: ...in SoftOff Hardoff 2 Indoor2 1 2 C 3 Offafter80min SoftOff Hardoff Premium 4 Offafter20min SoftOff Hardoff 5 Offafter40min SoftOff Hardoff 3 Indoor3 2 5 C 6 Offafter80min SoftOff Hardoff Standard 7 Of...

Страница 27: ...n number Units position of the option number Newvalue Indication and details Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 0 D Optio...

Страница 28: ...erature sensor Error of the discharge temperature sensor X X No communication for 2 minutes between indoor and outdoor unit communication error for more than 2 minutes X X Error of outdoor unit Error...

Страница 29: ...29 English Appendix Memo...

Страница 30: ......

Отзывы: