Outdoor unit
Input current (Amperes)
Power supply
Indoor unit
Outdoor unit
Rated
Voltage range
Outdoor unit
Indoor
unit
Total
MCA
MFA
Hz
Volts
Min.
Max.
Cooling
Heating
B
AC052MN4DKH/EU AC052MXADKH/EU
50
220 to 240 198
264
20
20
1.0
21.0
21.0
25.0
AC052NN4DKH/EU AC052MXADKH/EU
50
220 to 240 198
264
20
20
1.0
21.0
21.0
25.0
AC052MNNDKH/EU AC052MXADKH/EU
50
220 to 240 198
264
20
20
1.0
21.0
21.0
25.0
AC052NNNDKH/EU AC052MXADKH/EU
50
220 to 240 198
264
20
20
1.0
21.0
21.0
25.0
AC052MNMDKH/EU AC052MXADKH/EU
50
220 to 240 198
264
20
20
2.5
22.5
22.5
25.0
AC052MNLDKH/EU AC052MXADKH/EU
50
220 to 240 198
264
20
20
1.7
21.7
21.7
25.0
AC052MNCDKH/EU AC052MXADKH/EU
50
220 to 240 198
264
20
20
1.0
21.0
21.0
25.0
AC052MNJDKH/EU AC052MXADKH/EU
50
220 to 240 198
264
20
20
1.0
21.0
21.0
25.0
AC052MNADKH/EU AC052MXADKH/EU
50
220 to 240 198
264
20
20
1.6
21.6
21.6
25.0
AC060MNNDKH/EU AC060MXADKH/EU
50
220 to 240 198
264
20
20
1.0
21.0
21.0
25.0
AC060NNNDKH/EU AC060MXADKH/EU
50
220 to 240 198
264
20
20
1.0
21.0
21.0
25.0
AC060MNMDKH/EU AC060MXADKH/EU
50
220 to 240 198
264
20
20
2.5
22.5
22.5
25.0
C
AC071MN4DKH/EU AC071MXADKH/EU
50
220 to 240 198
264
20
20
1.0
21.0
21.0
25.0
AC071NN4DKH/EU AC071MXADKH/EU
50
220 to 240 198
264
20
20
1.0
21.0
21.0
25.0
AC071MN4PKH/EU AC071MXADKH/EU
50
220 to 240 198
264
20
20
1.5
21.5
21.5
25.0
AC071MNNDKH/EU AC071MXADKH/EU
50
220 to 240 198
264
20
20
1.0
21.0
21.0
25.0
AC071NNNDKH/EU AC071MXADKH/EU
50
220 to 240 198
264
20
20
1.0
21.0
21.0
25.0
AC071MNMDKH/EU AC071MXADKH/EU
50
220 to 240 198
264
20
20
2.5
22.5
22.5
25.0
AC071MNLDKH/EU AC071MXADKH/EU
50
220 to 240 198
264
20
20
1.7
21.7
21.7
25.0
AC071MNCDKH/EU AC071MXADKH/EU
50
220 to 240 198
264
20
20
1.0
21.0
21.0
25.0
AC071MNADKH/EU AC071MXADKH/EU
50
220 to 240 198
264
20
20
1.6
21.6
21.6
25.0
AC071MNMSEH/EU
AC071MXASEH/EU
50
220 to 240 198
264
20
20
3.5
23.5
23.5
25.0
D
AC100MNMSEH/EU
AC100MXASEH/EU
50
220 to 240 198
264
22
22
3.5
25.5
25.5
28.0
NOTE
1
Voltage range
• Units are suitable for use on electrical systems
where voltage supplied to unit terminal is not
below or above listed range limits
2
Maximum allowable voltage variation between
phases is 2%.
3
Wire size & type must comply with the applicable
local and national code.
• Wire size: Based on the value of MCA.
• Wire type: 60245 IEC57(IEC) or H05RN-
F(CENELEC) grade or more.
4
MFA is used to select the circuit breaker and the
ground fault circuit interrupter (earth leakage circuit
breaker).
5
MCA represents maximum input current.
• MFA represents capacity which may accept MCA
• Abbreviations
MCA: Min. Circuit Amps. (A)
MFA: Max. Fuse Amps. (A)