Installation Procedure
English
Ins
tallation Pr
oc
edur
e
CAUTION
• You should connect the power cable into the power
cable terminal and fasten it with a clamp.
• The unbalanced power must be maintained within 2%
of supply rating.
If the power is unbalanced greatly, it may shorten
the life of the condenser. If the unbalanced power
is exceeded over 4% of supply rating, the indoor
unit is protected, stopped and the error mode
indicates.
• To protect the product from water and possible shock,
you should keep the power cable and the connection
cord of the indoor and outdoor units within ducts.
(with appropriate IP rating and material selection for
your application)
• Ensure that main supply connection is made through
a switch that disconnects all poles, with contact gap
of a least 3 mm.
• Devices disconnected from the power supply should
be completely disconnected in the condition of
overvoltage category.
• Keep distances of 50 mm or more between power
cable and communication cable.
Main power terminal block specifications
1(L)
2(N)
L
N
Alimentación AC:
Tornillo M4
Comunicación:
Tornillo M4
F1
F2
,
,
,
,
Main power cable specifications
The power cable is not supplied with air conditioner.
• Select the power supply cable in accordance with relevant local and national regulations.
• Wire size must comply with the applicable local and national code.
• Specifications for local wiring power cord and branch wiring are in compliance with local cord.
Type
Model
Outdoor unit
Input current (Amperes)
Power supply
Indoor unit
Outdoor unit
Rated
Voltage range
Outdoor unit
Indoor
unit
Total
MCA
MFA
Hz
Volts
Min.
Max.
Cooling
Heating
A
AC026MN1DKH/EU AC026MXADKH/EU
50
220 to 240 198
264
10
10
1.0
11.0
11.0
12.5
AC026MNNDKH/EU AC026MXADKH/EU
50
220 to 240 198
264
10
10
1.0
11.0
11.0
12.5
AC026NNNDKH/EU AC026MXADKH/EU
50
220 to 240 198
264
10
10
1.0
11.0
11.0
12.5
AC026MNLDKH/EU AC026MXADKH/EU
50
220 to 240 198
264
10
10
1.7
11.7
11.7
12.9
AC026MNJDKH/EU AC026MXADKH/EU
50
220 to 240 198
264
10
10
1.0
11.0
11.0
12.5
AC026MNADKH/EU AC026MXADKH/EU
50
220 to 240 198
264
10
10
1.6
11.6
11.6
12.8
AC035MN1DKH/EU AC035MXADKH/EU
50
220 to 240 198
264
10
10
1.0
11.0
11.0
12.5
AC035MNNDKH/EU AC035MXADKH/EU
50
220 to 240 198
264
10
10
1.0
11.0
11.0
12.5
AC035NNNDKH/EU AC035MXADKH/EU
50
220 to 240 198
264
10
10
1.0
11.0
11.0
12.5
AC035MNMDKH/EU AC035MXADKH/EU
50
220 to 240 198
264
10
10
2.5
12.5
12.5
13.8
AC035MNLDKH/EU AC035MXADKH/EU
50
220 to 240 198
264
10
10
1.7
11.7
11.7
12.9
AC035MNJDKH/EU AC035MXADKH/EU
50
220 to 240 198
264
10
10
1.0
11.0
11.0
12.5
AC035MNADKH/EU AC035MXADKH/EU
50
220 to 240 198
264
10
10
1.6
11.6
11.6
12.8
AC052MNMSEH/EU
AC052MXASEH/EU
50
220 to 240 198
264
13
13
3.5
16.5
16.5
18.2