![Samsung AC MN KH/EU Series Скачать руководство пользователя страница 98](http://html1.mh-extra.com/html/samsung/ac-mn-kh-eu-series/ac-mn-kh-eu-series_technical-data-book_4088144098.webp)
Installation
98
Installation
1. Wind-Free 4Way Cassette (600x600)
Spacing requirements
1500 mm or more
Obstruction
1500 mm or
more
20 mm
17 mm
A
Model
AC026NNNDKH
AC035NNNDKH
AC052NNNDKH
AC060NNNDKH
AC071NNNDKH
A
297
(Unit: mm)
C: 1500 mm or more
C
C
C
C
CAUTION
•
The indoor unit must be installed according to the specified distances
in order to permit accessibility from each side, to guarantee correct
operation, maintenance, and repair of the unit. The components of the
indoor unit must be reachable and removable under safe conditions for
people and the unit.
•
Do not hold the discharge while carrying the indoor unit to avoid the
possibility of breakage.
•
You must hold the hanger plate on the corner and carry the indoor unit.
Step 3 Optional: Insulating the body of the
indoor unit
If you install a cassette type indoor unit on the ceiling when temperature is
over 27°C and humidity is over 80%, you must apply an extra 10 mm thick
polyethylene insulation or a similar type of insulation to the body of the
indoor unit.
Cut away the part where pipes are pulled out for the insulating work.
D
C
A
E
B
Insulate the end of the pipe and some curved area by using separate
insulator.
NOTE
• A: Reference for the outer circumference of the unit
(When insulating the body of the indoor unit, use A as the reference for
its outer circumference.)
A
B
C
D
E
400X190
400X190
400X190
400X190
550X550
Содержание AC MN KH/EU Series
Страница 8: ... 8 Contents Wind Free 4Way Cassette 600x600 9 Wind Free 4Way Cassette 34 Outdoor Units 68 ...
Страница 76: ...3 Centerof Gravity 76 OutdoorUnits AC071MXADKH Units mm inches AC090 100 120MXAD H Units mm inches ...