Installation
112
Items
Maximum allowable length
Outdoor unit models
AC090MXADKH
AC100MXADKH
AC100MXADNH
AC120MXADKH
AC120MXADNH
AC140MXADKH
AC140MXADNH
Main pipe (L1)
50 m
75 m
Max. height difference
between outdoor and
indoor units (h1)
30 m
30 m
L
1
h
1
n=1
indoor
Outdoor
•
Temper grade and minimum thickness of the refrigerant pipe
Outer diameter [mm]
Minimum thickness [mm]
Temper grade
ø6.35
0.7
C1220T-O
ø9.52
0.7
ø12.70
0.8
ø15.88
1.0
ø15.88
0.8
C1220T-1/2H OR
C1220T-H
ø19.05
0.9
ø22.23
0.9
CAUTION
•
Be sure to use C1220T-1/2H (Semi-hard) pipe for more than Ø19.05 mm.
If you use C1220T-O (Soft) pipe for Ø19.05 mm, the pipe may be broken,
which can result in an injury.
Make at least one round:
It will reduce noise and vibration
•
The appearance of the unit may be different from the diagram depending
on the model.
CAUTION
•
After connecting the pipes with knock-out treatment, plug the space
around the pipes.
•
After connecting the pipes, proceed exactly as directed in the guide to
prevent interference with the internal parts.