8.4.2 Terminal assignment
1
BA1
Binary output 1
230 V/2 A
2
BA2
Binary output2
230 V/2 A
3
COM1/2
COM binary output 1/2
4
BA3
Binary output 3
230 V/2 A
5
BA4
Binary output 4
230 V/2 A
6
COM3/4
COM binary output 3/4
7
AC1 24V
Power supply 24 V AC
AC 1
8
AC2 24V
AC 2 has GND reference
9
BE1
Binary input 1 or
0 to 10 V input
Or counter input
10
BE2
Binary input 2 or
0 to 10 V input
Or counter input
11
(
GND input 1/2
12
BE3
Binary input 3 or
Pt 1000 or 0 to 1000
Ω
13
BE4
Binary input 4 or
Pt 1000 or 0 to 1000
Ω
14
(
GND input 3/4
15
BE5
Binary input 5 or
0 to 10 V input
Or 0 to 10 V output
16
BE6
Binary input 6 or
0 to 10 V input
Or 0 to 10 V output
17
(
GND input/output 5/6
18
A1
RS-485/MODBUS (slave)
Connection to TROVIS 5571/5572
19
B1
20
A2
RS-485/MODBUS (master)
Connection to expansion module(s)
1)
21
B2
1)
Only with smart expansion module, functioning similar to a basis device
36
EB 5571 EN
Appendix
Содержание TROVIS 5571