7
| DOC9085G
SLP2100/2700/3100
2.2 Specifications
Description
Minimum
Maximum
Ambient temperature, operation
Below 0°C - see chapter 5.3
-20°C
55°C
Ambient temperature, storage
-20°C
55°C
Humidity
-
100%
Intake temperature, suction side
-
60°C
Intake temperature, water
-
60°C
Water pipe connection, dimension
1”
1½”
Water pipe connection, length
-
6 m
Noise level
-
80 dB(A)
Water volume
SLP 2100
55L / 20L
SLP 2700
64L / 24L
SLP 3100
71L / 28L
Maximum radial load on drive shaft
SLP2100/2700/3100
-
15000 N
Heat input for cooler calculation
SLP 2100
1200 rpm
30 kW
-
1300 rpm
35 kW
-
1400 rpm
40 kW
-
1500 rpm
44 kW
-
1600 rpm
51 kW
-
SLP 2700
1200 rpm
35 kW
-
1300 rpm
40 kW
-
1400 rpm
45 kW
-
1500 rpm
51 kW
-
1600 rpm
59 kW
-
SLP 3100
1200 rpm
42 kW
-
1300 rpm
45 kW
-
1400 rpm
51 kW
-
1500 rpm
59 kW
-
1600 rpm
68 kW
-
Revolutions
1200 rpm
1600 rpm
Pressure
200 mbar abs.
1 bar(g)
Lubricating grease
Type of grease
SKF LGWA2
Automatic lubrication
SKF LAGD 125/WA2
Weight
SLP 2100
350 kg
SLP 2700
390 kg
SLP 3100
420 kg
A failure to meet these specifications may result in damage to the pump