EB 2172 EN
9
Installation
Installation with thermowell
When a thermowell is used, a welding sock-
et with G 1 female thread must be used.
Î
Seal the thermowell into the welding
socket. Insert the sensor and tighten it
with the clamping screw.
Note:
For temperature regulators with safe-
ty temperature limiter (TR/STL), install
the sensor of the limiter near the sen-
sor of the regulator.
4.1.1 Capillary tube
Carefully run the capillary tube without
bending or twisting it. Avoid locations with
considerable ambient temperature fluctua-
tions along the entire length of the tube.
Note:
Do not damage or shorten the capil-
lary tube. Roll up any capillary tube
that is not used. The smallest permis
-
sible bending radius is 50 mm.
4.2
Strainer (filter)
Install the strainer upstream of the tempera-
ture regulator.
–
The flow of direction must correspond
with the direction indicated by the arrow
on the body.
–
The filter element must be installed to
hang downwards.
Tip:
Remember to leave enough space to
remove the filter element for clean
-
ing.
Fig. 2:
Typical installations
Type 43-5/43-7 in a steam-heated boiler
Type 43-6 in a cooler
1
Shut-off valve
2
Strainer
3
Temperature regulator
4
Thermometer
5
Temperature sensor
1
1
2 3
5 4
1
2 3
5
4