![Samson series 43 Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/samson/series-43/series-43_mounting-and-operating-instructions_3956820008.webp)
8
EB 2172 EN
Installation
4 Installation
Choose a place of installation that allows
you to freely access the regulator even after
the entire plant has been completed. Make
sure that the permissible ambient tempera-
ture does not fall below –20 °C or exceed
+80 °C.
Flush the pipeline thoroughly before install-
ing the regulator to ensure that any sealing
parts, weld spatter and other impurities car-
ried along by the process medium do not im-
pair the proper functioning of the valve,
above all the tight shut-off.
Note:
Type 43-5
/
Type 43-7
: If the valve is
to be insulated, two thirds of the insu-
lating pipe (1.3) must remain uninsu
-
lated.
–
Install the valve free of stress and with the
least amount of vibrations as possible.
–
The flow of direction must correspond
with the direction indicated by the arrow
on the valve body.
–
The control thermostat must be suspend-
ed to hang downward. Other mounting
positions are possible for Type 43-6 up
to 110 °C.
NOTICE
Malfunction and damage due to ad-
verse effects of weather conditions
(temperature, humidity).
Do not install the temperature regula-
tor outdoors or in rooms prone to
frost. If such a location cannot be
avoided, protect the regulator
against freezing up if the process
medium flowing through the valve
can freeze up. Either heat the regula
-
tor or remove it from the plant and
completely drain the residual medi-
um.
4.1 Temperature sensor
NOTICE
Galvanic corrosion due to incorrectly
selected materials of the mounting
parts.
On installing the sensor or thermow-
ell, only combine the same kind of
materials (e.g. stainless steel with
stainless steel or copper together with
other copper materials).
The temperature sensor may be installed in
any position even when a thermowell is
used. However, make sure its entire length is
immersed in the process medium to be con-
trolled. It must be installed in a location
where overheating or considerable idling
times cannot occur.
Note:
If the sensor is to be used with a ther-
mowell, only use original SAMSON
thermowells.
Weld a welding socket with G ½ or G ¾ fe-
male thread (to match the screw gland) at
the place of installation.
Î
Seal the screw gland of the sensor.
Содержание series 43
Страница 19: ......