Technical data
Positioner
Travel
Direct attachment to Type 3277
Attachment acc. to IEC 60534-6
Adjustable
7.5 to 30 mm
7.5 to 120 mm or 30 to 120° for rotary actuators
Bus connection
Fieldbus interface as per EN 61158-2, bus-powered
Physical Layer Class: 113 (not explosion-protected version) and 111 (Ex-version)
Field device according to FM 3610 entity and FISCO.
Permissible operating voltage
9 to 32 V DC
1)
, power supply over bus
Max. operating current
13 mA
Additional current in case of fault
0 mA
Supply air
Supply air from 1.4 to 6 bar (20 to 90 psi);
Air quality as per ISO 8573-1: Max. particle size and density: Class 4;
Oil contents: Class 3; Pressure dew point: Class 3
Signal pressure (output)
0 bar up to the pressure of the supply air
Characteristic, adjustable
Deviation
Globe valve: linear, equal percentage, reverse equal percentage,
SAMSON butterfly valve: linear, equal percentage
VETEC plug rotary valve: linear, equal percentage
≤
1 %
Dead band
(based on rated travel/angle
Adjustable from 0.1 to 10.0 % , default 0.5 %
Resolution (internal measurement) < 0.05 %
Transit time
For valve transit time up to 240 s, set point ramp for venting and supply air
separately adjustable
Operating direction
Reversible, setting by software
Air consumption
Independent of supply air <90l
n
/h
Air supply
Actuator filled: when
∆
p = 6 bar 9.3 m
n
3
/h, when
∆
p = 1.4 bar 3.5 m
n
3
/h
Actuator vented: when
∆
p = 6 bar 15.5 m
n
3
/h, when
∆
p = 1.4 bar 5.8 m
n
3
/h
Permissible ambient temperature
–40 to 80 °C
The specifications in the EC type examination certificate additionally apply for
explosion-protected devices
Effects
Temperature:
≤
0.15 %/10 K, supply air: none,
Vibrations: none up to 250 Hz and 4 g
Degree of protection
IP 65 using filter check valve included
Electromagnetic compatibility
Requirements acc. to EN 61000-6-2, EN 61000-6-3 and
NAMUR Recommendations NE 21 are met
Binary input
Internal power supply 5 V DC, R
i
= 100 k
Ω
for alarm function
Forced venting
(activated over an internal switch)
Input 6 to 24 V DC, R
i
approx. 6 k
Ω
at 24 V DC (depending on voltage)
Switching point for "1" signal
≥
3 V, switching point for "0" signal only at 0 V,
K
V
0.17
6
EB 8383-1 EN
Содержание foundation 3787
Страница 83: ...EB 8383 1 EN 83...
Страница 84: ...84 EB 8383 1 EN...
Страница 85: ...EB 8383 1 EN 85...
Страница 86: ...86 EB 8383 1 EN...
Страница 87: ...EB 8383 1 EN 87...
Страница 88: ...88 EB 8383 1 EN...
Страница 89: ...EB 8383 1 EN 89...
Страница 90: ...90 EB 8383 1 EN...
Страница 91: ...EB 8383 1 EN 91...
Страница 92: ...92 EB 8383 1 EN...
Страница 93: ...EB 8383 1 EN 93...
Страница 94: ...94 EB 8383 1 EN...
Страница 95: ...EB 8383 1 EN 95...