Start-up and settings
5. Briefly set the Tn restrictor to its minimum
setting (fully open) to allow the red con
-
trolled variable pointer to move to the
green set point pointer. Close the Tn re
-
strictor again.
6. Starting from a low value, increase the
proportional-action coefficient Kp until
the controlled variable pointer shows an
harmonic oscillation pattern of the con
-
trolled variable (uniform oscillation am
-
plitudes as shown in Fig. 4).
If oscillations do not arise with a large
Kp setting, turn the rotary knob to slight
-
ly change the set point and then return it
to its former setting. It may be necessary
to increase the gain (Kp) slightly until an
harmonic oscillation pattern arises.
7. Write down the adjusted value on the Kp
scale you have just adjusted as the criti
-
cal proportional-action coefficient Kp
crit
.
Use a stopwatch to time the oscillation
time for one entire oscillation to find T
crit
(PI and PID controllers only).
Fig. 4:
Harmonic oscillation, tuning
Multiply both values with the values in the ta
-
ble (Fig. 4) and set them as the favorable
settings for Kp, Tn and Tv at the controller.
Should oscillations still occur despite these
settings, slightly reduce Kp and increase Tn.
Repeat these steps, if necessary, until the
control loop shows a satisfactory perfor
-
mance.
Leave enough time in between settings to al
-
low the controller to stabilize.
4.2 Adjusting the operating
point in P and PD control-
lers
Type 3433 Controller Modules only
For P and PD controllers, after setting the
proportional-action coefficient Kp, set the
operating point instead of the reset time as
described above.
When the system is in a steady-state condi
-
tion, read the automatic output y
A
of the con
-
troller at the display (1.5) and set this value
directly at the operating point adjuster (12,
Fig. 1) (setting values 0.2 to 1 bar = 0 to
100 %).
Continue to correct until the system deviation
is zero. If the output pressure reading is un
-
steady, find the average value.
After the set point is changed, the operating
point must set again as described above.
When the set point is often changed, adjust
the operating point to 0.6 bar (e.g. 50 %,
average value).
Kp
Tn
Tv
P
0.50 · Kp
crit
PI
0.45 · Kp
crit
0.85 · T
crit
PID
0.59 · Kp
crit
0.50 · T
crit
0.12 · T
crit
Controlled
variable
(actual value)
T
crit
T
crit
–
+
Note
Содержание 430 Series
Страница 51: ...EB 7030 EN 51 Certificates 12 Certificates The ATEX certificates are included on the next pages...
Страница 52: ...52 EB 7030 EN...
Страница 53: ...EB 7030 EN 53...
Страница 54: ...54 EB 7030 EN...
Страница 55: ...EB 7030 EN 55...
Страница 56: ...56 EB 7030 EN...
Страница 57: ...EB 7030 EN 57...
Страница 58: ...58 EB 7030 EN...
Страница 59: ...EB 7030 EN 59...
Страница 60: ...60 EB 7030 EN...
Страница 61: ...EB 7030 EN 61...
Страница 62: ...62 EB 7030 EN...
Страница 63: ...EB 7030 EN 63...
Страница 64: ...64 EB 7030 EN...
Страница 65: ...EB 7030 EN 65...
Страница 66: ...66 EB 7030 EN...
Страница 67: ...EB 7030 EN 67...
Страница 68: ...68 EB 7030 EN...
Страница 69: ...EB 7030 EN 69...
Страница 70: ...70 EB 7030 EN...
Страница 71: ...EB 7030 EN 71...
Страница 72: ...72 EB 7030 EN...
Страница 73: ...EB 7030 EN 73...
Страница 74: ...74 EB 7030 EN...
Страница 75: ...EB 7030 EN 75...
Страница 76: ...76 EB 7030 EN...
Страница 77: ...EB 7030 EN 77...