EB 3003 EN
17
Appendix
10
Appendix
10.1
Technical data
Type
42-24 · 42-24
42-28 · 42-28
Nominal size
DN 15 to 250
DN 15 to 100
Nominal pressure
PN 16, 25 or 40
Max. permissible
temperature
Valve
See pressure-temperature diagram in
u
Actuator
1)
With compensation chamber: steam and liquids up to 350 °C
2)
Without compensation chamber: liquids up to 150 °C · Air and gases up to
80 °C
Set point ranges in bar
0.05 to 0.25 · 0.1 to 0.6 · 0.2 to 1 · 0.5 to 1.5
1 to 2.5 · 2 to 5 · 4.5 to 10
3)
0.2 · 0.3 · 0.4 or 0.5
Actuator area A
80 cm²
160 cm²
320 cm²
640 cm²
160 cm²
320 cm²
Pressure above adjusted set point at
which internal excess pressure
limiter responds
2.4 bar
1.2 bar
0.6 bar
0.3 bar
0.6 bar
0.3 bar
Max. perm. operating pressure for
actuator with two diaphragms
40 bar
40 bar
25 bar
25 bar
–
–
Leakage class according to
IEC 60534-4
≤0.05 % of K
VS
coefficient
1)
Higher temperatures on request
2)
Steam version only for valves balanced by a bellows
3)
DN 125 to 250: 4.5 to 10 bar on request
Terms for control valve sizing according to IEC 60534, Parts 2-1 and 2-2: F
L
= 0.95, X
T