32
EB 8395 EN
Malfunction
9
Malfunction
In case of a fault, the fault indication icon
is displayed.
If the fault indication icon appears after a
parameter code setting has been changed,
this indicates that this setting does not match
the values determined during initialization.
See Code
E1
(see code list in section 9.1).
Press buttons past Code
P0
or
P20.
The re-
spective error code
E0
to
E15
together with
ERR
appear on the display.
Refer to the code list for the cause of the er
-
rors and the recommended action.
Example:
If, for instance, a travel has been entered in
Code
P4
(nominal range) which is larger
than the maximum valve travel possible, the
initialization process would be interrupted
(
E2
error code) because the rated travel
would not have been reached (
E6
error
code). The valve moves to the fail-safe posi
-
tion (
S
indicated on the display).
mm
Display of the fault indica-
tion
The nominal range (Code P4) must be
changed and the positioner re-initialized to
remedy this problem.
Reset error codes
The E0 and E8 error codes can be reset as
follows:
Press
or to select the error code.
Press to confirm the error code.
ESC
is
displayed.
E8
blinks.
Press
or until
RST
appears.
Press
to reset the error.
The reset procedure can be canceled by
pressing when
ESC
appears.
Содержание 3724
Страница 39: ...EB 8395 EN 39...