3-4
EB 8060 EN
Design and principle of operation
3.4 Valve accessories
Information Sheet
u
3.5 Technical data
The nameplates on the valve and actuator
provide information on the control valve ver-
sion. See the 'Markings on the device' sec-
tion.
More information is available in Data Sheet
u
Optional RFID tag
Application range according to the technical
specifications and the explosion protection
certificates. These documents are available
on our website at
u
> Service & Support > Electronic nameplate
.
Conformity
The Type 3254 Valve bears both the CE and
EAC marks of conformity.
Temperature range
Depending on the version, the control valve
is designed for a temperature range from
–10 to +220 °C. The use of an insulating
section or bellows seal can extend the tem-
perature range from –196 to +550 °C de-
pending on the properties of the materials
used.
Leakage class
Depending on the version, the following
leakage class applies:
Seal (12 on
nameplate)
ME, ST
ME, ST
PT, PK
Pressure balanc-
ing (14 on name-
plate)
–
D/B
–
Leakage class
(according to
IEC 60534-4)
Min. IV Min. IV
VI
Noise emissions
SAMSON is unable to make general state-
ments about noise emissions. The noise emis
-
sions depend on the valve version, plant fa-
cilities and process medium.
Note
Содержание 3254
Страница 22: ...3 8 EB 8060 EN...
Страница 28: ...4 6 EB 8060 EN...
Страница 74: ...12 2 EB 8060 EN...
Страница 76: ...13 2 EB 8060 EN...
Страница 78: ...14 2 EB 8060 EN...
Страница 79: ...EB 8060 EN 14 3...
Страница 80: ...14 4 EB 8060 EN...
Страница 85: ......
Страница 86: ......
Страница 87: ......