Samson 2357-11 Скачать руководство пользователя страница 10

 10  

EB 2560 EN

Maintenance

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14

0

5

10

15

20

25

30

35

40

1...8 bar

5...2

5 bar

8...40 bar

Fig. 2: 

Adjustment diagram

5.3 

Decommissioning

Close first the shut-off valve on the upstream 

side of the valve and then on the down-
stream side of the valve.

Turns of the set point adjuster

: to increase the set point

: to reduce the set point

Set point 

[bar]

Maintenance

The regulators do not require any mainte-

nance. Nevertheless, they are subject to nat

-

ural wear, particularly at the seat, plug and 
operating diaphragm.
Depending on the operating conditions, 
check the regulator at regular intervals to 
avoid possible malfunctions.

WARNING!

Process medium can escape uncon-
trolled on dismantling the regulator.
Risk of cold burns!
Allow the regulator to defrost before 
depressurizing and draining it and re-
move it from the pipeline.

If faults or malfunctions cannot be remedied, 

contact SAMSON (see section 7).

6.1 

Exchanging the seat and 

plug

See Fig. 1 on page 7.

1.  Loosen the lock nut (11) and turn the set 

point adjuster (10) counterclockwise 

 to 

fully relieve the internal set point springs 
(8).

2.  Unscrew the body screws (14) using an 

open-end wrench (size 19 mm). Lift off 

the valve body (1).

3.  Unscrew the seat (15) using a seat 

wrench (size 30 mm socket). Remove the 

plug (2.1).

Set point ranges

Содержание 2357-11

Страница 1: ...tructions EB 2560 EN Edition August 2014 Type 2357 11 Pressure Build up Regulator Type 2357 21 Excess Pressure Valve Self operated Pressure Regulators Type 2357 11 Pressure Build up Regulator Type 235...

Страница 2: ...h if not avoided will result in death or seri ous injury WARNING Hazardous situations which if not avoided could result in death or se rious injury NOTICE Property damage message or mal function Note...

Страница 3: ...tion 6 4 Installation 8 4 1 Mounting position 8 4 2 Shut off valve 8 5 Operation 8 5 1 Start up 8 5 2 Set point adjustment 8 5 2 1 Changing the set point range 9 5 3 Decommissioning 10 6 Maintenance 1...

Страница 4: ...ence as well as their knowledge of the applicable standards The regulators comply with the requirements of the European Pressure Equip ment Directive 97 23 EC The declaration of conformity issued for...

Страница 5: ...to the adjusted set point especial ly in cryogenic plants WARNING Risk of injury and property damage due to high pressure in the plant A suitable overpressure protection must be installed on site in...

Страница 6: ...r 10 The valve closes when the pres sure upstream of the valve port B increases Type 2357 11 Pressure Reducing Valve The process medium flows from port A to port B when the Type 2357 11 Pressure Reg u...

Страница 7: ...phragm 4 1 Gasket bottom section of the body 5 Diaphragm plate 6 Ball 7 Spring plate 8 Set point springs 9 Spring housing bottom section of the body 10 Set point adjuster hexagon socket 5 mm 11 Lock n...

Страница 8: ...357 11 Pressure Reducing Valve Direction of flow from port A to port B Type 2357 21 Excess Pressure Valve with with non return unit A B Direction of flow from port B to port A The ports are marked Req...

Страница 9: ...to move free ly 2 Determine the difference between the fixed set point Table 1 and the required set point Turn the set point adjuster 10 the required amount of turns as specified in Fig 2 on page 10 B...

Страница 10: ...the operating conditions check the regulator at regular intervals to avoid possible malfunctions WARNING Process medium can escape uncon trolled on dismantling the regulator Risk of cold burns Allow...

Страница 11: ...point adjuster 10 counterclockwise to fully relieve the internal set point springs 8 2 Unscrew the body screws 14 using an open end wrench size 19 mm Lift off the valve body 1 3 Unscrew the integrated...

Страница 12: ...ww samson de in all SAMSON product catalogs or on the back of these Mounting and Operating Instructions Please send your inquiries to service samson de To assist diagnosis and in case of an unclear mo...

Страница 13: ...s and weights 9 Dimensions and weights 100 140 140 51 G A Type 2357 11 Pressure Regulator Type 2357 21 Excess Pressure Valve with welding ends accessories Weight approx 4 kg All dimensions in mm Fig 4...

Страница 14: ...ng pressure pmax 63 bar 2 Safety function for Type 2357 11 5 bar above the set point Max perm differential pressure pmax Types 2357 11 Pressure Reducing Valves Gases 30 bar Liquids 6 bar Type 2357 21...

Страница 15: ...EB 2560 EN 15...

Страница 16: ...SAMSON AG MESS UND REGELTECHNIK Weism llerstra e 3 60314 Frankfurt am Main Germany Phone 49 69 4009 0 Fax 49 69 4009 1507 samson samson de www samson de EB 2560 EN 2014 09 16 English...

Отзывы: