13
Ground Fault Circuit Interrupters (GFCI)
Installations in Recreational Vehicles (for North American approvals) will
require GFCI protection of all branch circuit connected to the AC output of
the hardwire terminal equipped with Inverter. In addition, electrical codes
require GFCI protection of certain receptacles in residential installations.
While the pure sine wave output of the Inverter is equivalent to the waveform
provided by utilities, compliance with UL standards requires us to test and
recommend specific GFCI.
Samlex has tested the following GFCI – protected 20A receptacles and found
that they functioned properly when connected to the output of the Inverter.
3-6. DC Wiring Connections
:
Follow this procedure to connect the battery cables to the DC input terminals
on the Inverter. The cables should be as short as possible (less than 10
feet / 3 meters ideally) and large enough to handle the required current in
accordance with the electrical codes or regulations applicable to the
installation.
Cables that are not an adequate gauge (too narrow) or too long will
deteriorate inverter performance such as poor surge capability and frequent
low-input voltage warnings and shutdowns.
These low input voltage warnings are due to DC voltage drop across the
cables from the inverter to the batteries.
The linger and narrower the cables, the greater the voltage drops.
WARNING!
Do not operate the power inverter without connecting
it to ground. Electrical shock hazard may occur.
WARNING!
The fuse must be installed on positive cable.
Failure to place a fuse on “+” cables running between
the inverter and battery may cause damage to the
inverter and will void warranty.