INSTALLATION

Page 19

GENERAL
Installation and wiring compliance

-  Installation and wiring must comply with the local and the national electrical codes and

must be done by a certified electrician

-  In building / residential applications, electrical codes do not allow permanent connection

of AC distribution wiring to the inverter’s AC output receptacles. The receptacles are
intended for temporary (as needed) connection of cord connected loads only. 

Read

details under “AC Power Distribution and Grounding” on page 9.

-  The inverter does not have integral over current protection for the AC output side.

Protection should be provided by the installer

-  Over current protection of the cables from the battery to the inverter has to be provided

by the installer

-  The DC input positive and negative terminals are isolated from the chassis. Similarly, the

neutral pole of the AC receptacles / the neutral wire is not bonded to the chassis. System
grounding to suit the national / local electrical codes is to be undertaken by the installer.

Read details under“AC Power Distribution and

 

Grounding” on page 9.

Preventing electrical shock

- Always connect the grounding connection on the inverter to the appropriate grounding

system. 

Read details under“AC Power Distribution and

 

Grounding” on page 9.

Installation environment

-  The inverter should be installed indoor only in a well ventilated, cool, dry environment
-  Do not expose to moisture, rain, snow or liquids of any type.
-  To reduce the risk of overheating and fire, do not obstruct the suction and discharge

openings of the cooling fans.

-  To ensure proper ventilation, do not install in a low clearance compartment
-  Working with the inverter may produce arcs or sparks. Thus, the inverter should not be

used in areas where there are inflammable materials or gases requiring ignition protected
equipment. These areas may include spaces containing gasoline powered machinery, fuel
tanks, battery compartments

Mounting position of the inverter
-

The inverter may be mounted horizontally on the top of a horizontal surface or under a
horizontal surface. The inverter may be mounted on a vertical surface only horizontally

(the fan axis should always be horizontal i.e. the fans should not be pointing up or down)

Cooling by forced air fan ventilation

The inverters produce heat when operating. The amount of heat produced is proportional to
the amount of power supplied by the inverter. Two DC fans are used to provide forced air
cooling of this inverter. The fans are thermostatically controlled and will be switched on
only if the temperature of certain hot spot inside the inverter rises above a certain tempera-
ture. 

At lower loads and / or at lower ambient temperatures, the fans may not switch on at all.

This is normal.

 

The unit is protected against over-temperature due to failure of the fan(s) /

inadequate heat transfer. The AC output will be shut-down if the hot spot inside the
inverter reaches a certain higher temperature.

Содержание PST-200S-12A

Страница 1: ...Please read this manual before operating your inverter PURE SINE WAVE DC AC INVERTER MODELS PST 200S 12A PST 200S 24A A C P O W E R S O U R C E OWNER S MANUAL ...

Страница 2: ...tion and Grounding 9 10 11 Limiting Electromagnetic Interference EMI 11 Powering direct embedded SMPS 12 Principle of Operation 13 Layout 13 Specifying Batteries Chargers and Alternators 14 15 16 17 18 Installation 19 20 21 22 23 Operation 24 25 Protection Against Abnormal Conditions 25 26 Troubleshooting Guide 27 28 Specifications 29 Warranty 30 INDEX Page 1 ...

Страница 3: ...ns To ensure proper ventilation do not install in a low clearance compartment Preventing fire and explosion hazards Working with the inverter may produce arcs or sparks Thus the inverter should not be used in areas where there are inflammable materials or gases requiring ignition protected equip ment These areas may include spaces containing gasoline powered machinery fuel tanks battery compartmen...

Страница 4: ...e transformer isolated or auto transformer of suitable wattage rating 25 more than the wattage rating of the inverter with primary of 120 VAC and secondary of 120 240 VAC Two 120 VAC split phases 180 degrees apart should be used The hot and neutral of the 120 VAC output of the inverter should be fed to the primary of this trans former and the 2 hot outputs 120 VAC split phases and the neutral from...

Страница 5: ...able for use in buildings including homes for recreational vehicles boats and portable applications Will it be connected to the utility grid in some way Electrical conventions and safety standards differ for various applications so don t improvise Electrical Standards The DC input voltage must conform to that of the electrical system and battery bank 12 volts is recommended for small simple system...

Страница 6: ...rter will further limit its ability to start a motor A battery bank that is undersized in poor condition or has corroded connections can be a weak link in the power chain The inverter cables and the battery interconnect cables must be sized properly The spike of DC current through these cables is many hundreds of amps at the instant of motor starting Please follow the instructions under Installati...

Страница 7: ...0 VAC To obtain 240 VAC from a 120 VAC inverter use a 120 VAC to 240 VAC transformer If you do not already have a pump installed you can get a 120 volt pump if you don t need more than 1 2 HP Idle power Idle power is the consumption of the inverter when it is on but no loads are running It is wasted power so if you expect the inverter to be on for many hours during which there is very little load ...

Страница 8: ...istive type of loads that have unity 1 Power Factor In a reactive type of load like electric motor driven loads fluorescent lights computers audio video equipment etc the phase of the sine wave form of the current drawn by the load may lead or lag the sine wave form of the AC voltage source In this case the power factor of reactive loads is lower than unity 1 generally between 0 8 and 0 6 A reacti...

Страница 9: ... wave form is a sine wave with very low harmonic distortion and clean power like utility supplied electricity Inductive loads like microwaves and motors run faster quieter and cooler Reduces audible and electrical noise in fans fluorescent lights audio amplifi ers TV fax and answering machines Prevents crashes in computers weird print outs and glitches in monitors Some examples of devices that may...

Страница 10: ...cted to earth Examples are the neutral conductor in AC wiring and the negative conductor in many DC systems A grounded system is a system in which one of the current carrying conductors is grounded An equipment grounding conductor is a conductor that does not normally carry current except under fault conditions and is also connected to earth It is used to connect the exposed metal surfaces of elec...

Страница 11: ...onnection to the AC power source The plug of the power cord has three pins two flat pins also called poles that are connected to the two current carrying conductors and a round pin which is connected to a non current carrying conductor this will carry current only during ground fault conditions One flat pin is connected to a black current carrying conductor which is also called Line Live Hot pole ...

Страница 12: ...t be tight against bare metal Use star washers to penetrate paint and corrosion The inverter contains internal switching devices which generate conducted and radiated electromagnetic interference EMI The magnitude of EMI is limited to acceptable levels by circuit design but can not be entirely eliminated The effects of EMI will also depend upon a number of factors external to the power supply like...

Страница 13: ...of up to 4 This will mean that for a particular rated RMS current applicable for a linear load the general purpose SMPS will draw much larger peak currents approx up to 4 times more than its rated RMS current Inverters are protected against over current also called overloading by either clipping the peaks of the output voltage this will result in a sine wave becoming a square wave reduction in the...

Страница 14: ...ave AC again using PWM technique This is done by using a special wave shaping technique where the high voltage DC is switched at a high frequency and the pulse width of this switching is modulated with respect to a reference sine wave 1 125 V 20 A NEMA5 20R AC output receptacles 2 Power on off Switch 3 Green L E D Power output status 4 Red L E D Overload 5 Red L E D Over temperature 6 Input termin...

Страница 15: ...of deep cycle lead acid batteries wet and sealed A wet cell battery has a high tolerance to overcharg ing However it will release hydrogen gas when charging that must be properly vented and the water level must be checked frequently Sealed batteries can either be Gel Cell or AGM Absorbed Glass Mat Both the Gel Cell and AGM are maintenance free have no liquid to spill and gassing is minimal The Gel...

Страница 16: ...p is not linear but is more or less according to the table below Table 1 Battery Capacity versus Rate of Discharge Hours of Discharge Usable Capacity 20 100 10 87 8 83 6 75 5 70 3 60 2 50 1 40 Using the above table will show that a 100 AH capacity battery will deliver 100 i e full 100 AH capacity if it is slowly discharged over 20 hours at the rate of 5 Amperes However if it is discharged at a rat...

Страница 17: ...allel connection of batteries When two or more batteries are connected in series their voltages add up but their AH capacity remains the same For example when two 12 V 105 AH batteries are connected in series it becomes a 24 V 105 AH battery Positive of the first battery is the positive terminal of the series connection The negative of the first battery is connected to the positive of the second b...

Страница 18: ... by multiplying 120 VAC by the AC current in Amperes The next step is to derive the DC current in Amperes A from the AC watts as per formulae 2 above An example of this calculation for a 12V inverter is given below Let us say that the total AC Watts delivered by the12 V inverter 1000 W Then using formula 2 above the DC current to be delivered by the 12 V batteries 1000 W 10 100 Amperes Next the en...

Страница 19: ...SLI and the auxiliary deep cycle batteries the output from the alternator should be fed to these two sets of batteries through a battery isolator of appropriate capacity The battery isolator is a solid state electronic circuit that will allow the alternator to charge the two sets of batteries when the engine is running The isolator will allow the inverter to be operated from the auxiliary batterie...

Страница 20: ... dry environment Do not expose to moisture rain snow or liquids of any type To reduce the risk of overheating and fire do not obstruct the suction and discharge openings of the cooling fans To ensure proper ventilation do not install in a low clearance compartment Working with the inverter may produce arcs or sparks Thus the inverter should not be used in areas where there are inflammable material...

Страница 21: ... Please observe the following precautions Ensure that the maximum charging voltage of the battery charger alternator solar charge controller is below 16 5 VDC for PST 200S 12A or 33 VDC for PST 200S 24A Do not use unregulated solar panels to charge a battery Under cold ambient tempera tures the output of the solar panel may exceed 18 V for 12V system or 36 V for 24V system Always use a charge cont...

Страница 22: ... 12A AWG 1 0 AWG 2 0 300A ANN 300 PST 200S 24A AWG 4 AWG 2 150 A ANN 150 CAUTION The input section of the inverter has large value capacitors connected across the input terminals As soon as the DC input connection loop Battery Y Y Y Y Yfuse Y Y Y Y Y inverter Y Y Y Y Yinverter Y Y Y Y Ybattery negative is completed these capacitors will start charging and will momentarily draw very heavy current t...

Страница 23: ...erter and this panel is also required to be powered from additional alternate AC sources the AC power from all the AC sources like the utility generator inverter should first be fed to a manual selector switch and the output of the selector switch should be connected to the electrical breaker panel load center To prevent possibility of paralleling and severe damage to the inverter never use a simp...

Страница 24: ... burned severely shocked or electrocuted A GFCI protects people from electric shock by detecting leakage and cutting off the AC source The AC output to the 2 NEMA 5 20R receptacles is fed through a built in GFCI The GFCI will shut down the AC ouput if it detects any leakage current 5 mA Grounding to earth or to other designated ground Please see details regarding grounding under AC Power Distribut...

Страница 25: ...circuit will still be alive even when the switch is in the off position Hence disconnect the DC and AC sides before working on any circuits connected to the inverter When the inverter is switched on the green LED indicator 3 will be lighted This LED indicates that the inverter is operating normally Under normal operating conditions AC output voltage will now be available at the output receptacles ...

Страница 26: ...ere will be a no load current Therefore to prevent any drain from the battery switch off the inverter from the on off switch provided on the front panel of the inverter The inverter has been provided with protections detailed below Low DC input voltage warning alarm The voltage at the DC input terminals will be lower than the voltage at the battery terminals due to the voltage drop in the battery ...

Страница 27: ...rature inside the unit will increase The temperature of a critical hot spot inside the inverter is monitored and at a particular upper limit the AC output of the inverter is shut down temporarily The red Over Temp LED 5 is lighted and a buzzer is sounded The unit will automatically reset after the unit has cooled down Shut down due to overload The inverter can provide a higher than normal instanta...

Страница 28: ... 3 Check that all connections in the battery input circuit are tight Visibly check the fuse element if it is blown The fuses are soldered and are not easily replaceable CallTechnical Support for repair 1 Check that the battery is fully charged Recharge if low 2 Check that the battery cables are thick enough to carry the required current over the required length Use thicker cables if required 3 Tig...

Страница 29: ...e load completely the unit has become defective Call Technical support 1 Check for ground fault in the load circuit A ground fault will cause a minor shock on touching Note In both the cases the unit will be latched in this shut down condition To reset switch the power on off switch to off and then on again Before switching on again remove the cause of the shut down 1 Check that the fans are worki...

Страница 30: ...e of loads will reduce by this factor See page 7 for details Low Input Voltage Warning Alarm 10 7 V 21 4 V Low Input Voltage Shut down 10 V 20 V High Input Voltage Shut down 16 5V 33V Leakage Protection Built in Ground Fault Circuit Interrupter GFCI OperatingAmbient Temp 0 to 40o C 5o C 0 to 40o C 5o C Peak Efficiency 85 85 Cooling 2 xTemperature Controlled Fans Connections Input Tubular type scre...

Страница 31: ...y attempt to remedy the defect by anyone other than the Warrantor shall render this warranty void There shall be no warranty for defects or damages caused by faulty installation or hook up abuse or misuse of the equipment including exposure to excessive heat salt or fresh water spray or water immersion No other express warranty is hereby given and there are no warranties which extend beyond those ...

Страница 32: ...110 17 Fawcett Road Coquitlam B C Canada V3K 6V2 e mail samlex samlexamerica com website www samlexamerica com Version PST 200S 12A_24A Nov2007 ...

Отзывы: