SECTION 11 |
Troubleshooting Guide
11.2 PST-600-48
ISSUE
POSSIBLE CAUSE
REMEDY
When switched ON, the
Green LED marked "POWER
ON" (2, Fig 6.2 does not
light. Buzzer is OFF. There is
no AC output voltage. Green
indication light on the GFCI
is OFF.
There is no voltage at the
DC input terminals
• Check the continuity of the battery
input circuit.
• Check that the internal/external battery
fuses are intact. Replace if blown.
• Check that all connections in the battery
input circuit are tight.
Polarity of the DC input
voltage has been reversed
that has blown the exter-
nal / internal DC side fuses
(
Note: Reverse polarity
may cause permanent
damage
. Damage caused
due to reverse polarity is
not covered by warranty)
• Check external and internal fuses. Replace
fuses. If unit does not work, call Technical
Support for repair.
Low AC output voltage
(< 120VAC but > 80VAC)
(No buzzer alarm).
• AC load is exceeding
Surge Overload of 166%
• Load is approaching
Surge Overload of 166%
during lower DC input
voltage
• Check that the battery is fully charged.
Recharge, if low.
• Check that the battery cables are thick
enough to carry the required current over
the required length. Use thicker cables, if
required.
• Tighten connections of battery input circuit.
• Reduce load.
AC output voltage is available.
Buzzer alarm is sounded at no
load or, when load is switched
ON. The Green LED marked
"POWER ON" (2, Fig 6.2) is
lighted. Indication light on the
GFCI is Green.
• Low DC input voltage
alarm
• DC input voltage is 42.0
±
0.5 VDC or lower but
higher than 40.0
±
0.5
VDC
• Check that the battery is fully charged.
Recharge, if low.
• Check that the battery cables are thick
enough to carry the required current over
the required length. Use thicker cables, if
required.
• Tighten connections of the battery input
circuit.
There is no AC output voltage.
Buzzer alarm is sounded at no
load or when load is switched
ON. The Green LED marked
"POWER ON" (2, Fig 6.2)
is lighted. GREEN indication
light on the GFCI is OFF. There
is no AC output.
• AC output voltage has
been shut down due to
low DC input voltage
• DC input voltage is 40.0
±
0.5 VDC or lower
• Check that the battery is fully charged.
Recharge, if low.
• Check that the battery cables are thick
enough to carry the required current over
the required length. Use thicker cables, if
required.
• Tighten connections of the battery input
circuit.
• The AC output voltage will switch ON auto-
matically when the DC input voltage rises to
46.0
±
0.5 VDC or higher.