3. Layout of the EVO
TM
• Refer to Section 2 starting at page 28 of the EVO
TM
Owner’s manual to become familiar
with all the relevant connection points and components.
4. Mounting the Units
• Refer to mounting information at Section 3.3 starting at page 32 of the EVO
TM
Owner’s
Manual
• Plan a safe location and routing of wiring for the associated components
• Ensure the mounting surface is strong enough to support the weight of at least
60Kg/132lbs
• Ensure that the mounting location is cool, dry and allows unobstructed air flow for cooling
• Mounting requires four (quantity 4) M6 or ¼” bolts to secure the inverter horizontally or
vertically on a wall with at least 8”/200 mm clearance around the unit. All dimensional
information is shown in Fig 3.1 at page 32 of the EVO
TM
Owner’s Manual.
!
CAUTION!
PLAN SYSTEM GROUND AND GROUND FAULT PROTECTION PRIOR TO INSTALLATION
• Ensure that the entire installation is properly grounded to meet Local and National Electrical Codes.
• Refer to typical grounding arrangement at Fig 3.15 at page 65 of the EVO
TM
Owner’s Manual.
• Ensure that the AC Neutral is bonded to the Earth Ground at only one point.
5. Plan the Battery Bank
• Select the type and size of the battery bank and bank configuration. Refer to Section 3.4
starting at page 34 of the Owner’s Manual regarding installation of batteries.
• Determine the overall Ah capacity (C) of the battery bank.
• Check with the battery manufacturer regarding maximum recommended charging
current. The factory default “Bulk Current” parameter is set to 40A.
• Locate an appropriate area for the battery bank and cable routing to the EVO
TM
.
• The EVO
TM
comes with a battery temperature sensor model EVO-BTS. This sensor
provides information to the charging algorithm to ensure a proper and safe charge to
the battery. Refer to Section 2.5 starting at page 31 of the EVO
TM
Owner’s Manual.
• An appropriately sized DC disconnect switch is recommended.
6. Select and procure the appropriate wire size and lengths for the intended type of
installation along with the appropriate breaker/fuse sizes
• For sizing the AC input wiring and breakers, refer to TABLES 3.2.1 and 3.2.2 at page
50 and TABLE 3.2.3 at page 51 of the EVO
TM
Owner’s Manual.
• For sizing the AC output wiring and breaker, refer to TABLE 3.3 at page 53 of the
EVO
TM
Owner’s Manual.
• For sizing the DC (Battery side) wiring and fuse, refer to TABLE 3.1 at page 43 of the
EVO
TM
Owner’s Manual.
EVO