IDC360iM 1224 V2.0 -  20211103 EN

 

 

 

 

Features 

IDC360iM 1224 V 2.0 

 

 

Galvanic isolated input and output 

Very low power consumption 

 

Easy installation 

Integrated vibration detection 

 

 Purpose 

The IDC360iM 1224 V 2.0 is an intelligent galvanically isolated inverter that is intended for the correct 

charging of a secondary battery system. The IDC360iM 1224 V 2.0 is equipped with voltage detection and 

a sensor that can detect vibrations. Based on the measured voltage and /or vibrations, the IDC360iM 1224 

V 2.0 can detect whether a vehicle is 'on'. 

 Installation  

 

 

 

 

 

 

Wiring diagram 

Warnings:

 

The product must only be connected by skilled 

fitters/mechanics who are aware of the 

regulations for working with high battery voltages. 

The product may be damaged if you use inferior 

connection material and/or wiring that is too thin. 

A short circuit between the positive and negative 

terminals of the battery may cause severe 

damage to your system. Always use fuses of the 

correct value.

 

 Operation 

The IDC has three different modes: 

Charge,

 

Standby

 and 

Off

.

 

 

After connecting, the converter will be in “Off mode” if the voltage is lower than 12.6V. There i

s no voltage 

on the output and the primary/yellow LED flashes at a frequency of 1Hz. The secondary/green LED is off. 

 

The converter will enter “Charge Mode” if at least one of the following two conditions is met:

 

• Vibration is detected AND the input volta

ge is (5sec) above 11.8V. 

• There is no vibration AND the input voltage is (5sec) above 12.6V.

 

 

The converter delivers 28.8 V at the output in the “Charge mode” and both the primary/yellow and the 

secondary/green LED are on. 

 

When a voltage of 28.4 V is measured on the output, a timer will start and runs for an hour. After this hour, 

the IDC will be set to the "Standby mode". The IDC output will be 27.4 V in the "Standby mode" and both 

the primary/yellow and the secondary/green LED are on. 

The IDC will return to the "Charge mode" if: 

 

The voltage on the output falls below 26.4 V (for 5 s). 

 

The IDC has been in the "Standby mode" for 24 continuous hours. 

 

The IDC will be set to the "Off mode" from both the "Charge mode" and "Standby mode" if: 

• There is vib

ration AND the input voltage is (5min) below 11.8V. 

• There is vibration AND then the input voltage is (10sec) below 11.6V.

 

• There is no vibration AND then the input voltage is (10min) below 12.4V.

 

• There is no vibration AND then the input voltage is (3s

ec) below 12.0V. 

 

 

 

 

 