background image

SWITCH 2005GT 

Quick Installation Guide

 

-1-

-2-

-3-

1. Overview

SWITCH 2005GT Unmanaged Industrial Ethernet Switch is 

specially designed to expand reliable Ethernet connectivity to 

factory  floors  and  outdoor  environments  with  extreme 

temperature and climatic conditions.
SWITCH 2005GT is equipped with 5 x 10/100/1000 RJ45 Ports 

enclosed in IP30 housing.

4. Grounding the switch SWITCH 2005GT

!

ATTENTION:  

This product is intended to be mounted to a well- 

grounded mounting surface such as a metal panel.

!

WARNING:

Safety measures should be taken before connecting 

the power cable.Turn off the power before connecting 

modules or wires. The correct power supply voltage is listed on 

the product label. Check the voltage of your power source to 

make sure that you are using the correct voltage. DO NOT use a 

voltage  greater  than  what  is  specified  on  the  product  label. 

Calculate the maximum possible current in each power wire and 

common wire. Observe all electrical codes dictating the 

maximum current allowable for each wire size. If current 

exceeds the maximum rating, the wiring can overheat causing 

serious damage to your equipment.

Please read and follow these guidelines: 

•  Use separate paths to route wiring for power and devices. If 

power wiring and device wiring paths must cross make sure 

the wires are perpendicular at the intersection point

  NOTE: Do not run signal or communications wiring and power 

wiring through the same wire conduit. To avoid interference, 

wires  with  different  signal  characteristics  should  be  routed 

separately

•  You can use the type of signal transmitted through a wire to 

determine which wires should be kept separate. The rule of 

thumb is that wiring that shares similar electrical characteris-

tics can be bundled together 

•  You should separate input wiring from output wiring

•  We advise that you label the wiring to all devices in the system

Removing the Switch

Mounting the Switch

Click

Dismounting the switch

Press the switch from top and pull out the lower edge of the 

switch and then remove the switch from the DIN rail.

Mounting the switch

Place the SWITCH 2005GT on the DIN rail from above using the 

slot, push the front of the switch toward the mounting surface 

until it snaps into place with a click sound.

Check the polarity while connecting.
Top view of Terminal Block is shown in the figure below:

Grounding and wire routing help limit the effects of noise due to 

electromagnetic interference (EMI). 
Step 1: Run the ground connection from the ground screw to 

 

the grounding surface prior to connecting devices. 

Step 2: Connect the ground connection from the terminal block 

 

to the grounding surface prior to connecting device.

5. Wiring requirements

5.1 Wiring Power Input

5.1.1 SWITCH 2005GT with 3pin terminal block

!

Caution:  

•  Use copper conductors only

•  Wiring cable temperature should support at 

least 105˚C 

•  Tighten the wire to a torque value 20N

•  The wire gauge for the terminal block should 

range between 0.2 to 2.5 mm

2

-

Grounding

Screw

Power

Power input terminals

Grounding terminals

2. Package Checklist

• SWITCH 2005GT Switch x 1

3. Mounting and Dismounting to DIN-Rail

!

ATTENTION:  

The SWITCH 2005GT ia an open type device and 

SWITCH 2005GT shall be DIN-Rail mounted in cabinet 

or enclosure and the ambient temperature should not 

exceed 75 °C.

Panel view

PWR

+

12~48VDC

Front View

10/100

1

2

3

4

5

1000

10/100

1000Mbps

Top View

Grounding

Screw

Power

PWR

+

9~48VDC

Отзывы: