PRESSING IT FOR MORE THAN 1s
YOU GO OUT OF THE SETUP AND
THE PARAMETERS ARE STORED
IN THE MEMORY
PRESSED IT DISPLAYS THE
REMAINING PART OF THE
PARAMETERS SEE CHAPTER 5.4
5.2 Application 4-20mA bar
5. PROGRAMMING
28
TRASDUTTORE
10 bar
TRASDUTTORE
10 bar
TRASDUTTORE
16 bar
IT IS USED TO SET THE FULL
SCALE OF THE TRANSDUCER
USED
PRESSIONE START1
3.0 bar
PRESSIONE START1
3.0 bar
IT IS USED TO SET THE
PRESSURE REQUIRED TO
START THE FIRST MOTOR
IT IS USED TO SET THE
PRESSURE REQUIRED TO
START THE SECOND MOTOR
TRASDUTTORE
25 bar
TRANSDUCER 10bar: 0.1 ÷ 8bar
TRANSDUCER 16bar: 0.1 ÷ 14bar
TRANSDUCER 25bar: 0.1 ÷ 23bar
5.1
PRESSIONE EMERG.
2.0 bar
PRESSIONE EMERG.
2.0 bar
TRANSDUCER 10bar: 0.1 ÷ 8bar
TRANSDUCER 16bar: 0.1 ÷ 14bar
TRANSDUCER 25bar: 0.1 ÷ 23bar
DELTA PRESSIONE
1.0 bar
DELTA PRESSIONE
1.0 bar
TRANSDUCER 10bar: 0.1 ÷ 8bar
TRANSDUCER 16bar: 0.1 ÷ 14bar
TRANSDUCER 25bar: 0.1 ÷ 23bar
TRANSDUCER 10bar: 0.1 ÷ 8bar
TRANSDUCER 16bar: 0.1 ÷ 14bar
PRESSIONE MINIMA
OFF
PRESSIONE MINIMA
OFF
TRANSDUCER 25bar: 0.1 ÷ 23bar
PRESSIONE START2
2.5 bar
PRESSIONE START2
2.5 bar
IT IS USED TO SET THE
NECESSARY PRESSURE
TO START THE RESCUE MOTOR
TRANSDUCER 10bar: 0.1 ÷ 8bar
TRANSDUCER 16bar: 0.1 ÷ 14bar
TRANSDUCER 25bar: 0.1 ÷ 23bar
PRESSIONE MINIMA
0.5 bar
IT IS USED TO SET THE
PRESSURE THAT ADDED TO
THE "START 1 PRESSURE"
STOPS THE MOTOR
IT IS USED TO SET THE REQUIRED
PRESSURE BELOW WHICH THE
MOTORS STOP. AT THE MOTORS’
STARTING THIS PARAMETER IS
BYPASSED FOR 1 MINUTE
OFF
EXCLUDES
MINIMUM PRESSURE