18
6.
GENERAL FUNCTIONING OF THE CONTROL PANEL
IGNITION
CONTROL PANEL
6.1
General functioning
ON
WAITING 10s
MANUAL OPERATION:
IT IS ACTIVATED FROM THE
STOP
STATUS BY HOLDING THE BUTTON PRESSED.
IN THIS CONDITION THE CONTROL PANEL STARTS THE MOTOR UNTIL THE BUTTON IS RELEASED EXCLUDING
THE CONTROL ON THE AUTOMATIC. RELEASING THE BUTTON YOU RETURN TO THE
STOP
STATUS
AUTOMATIC OPERATION:
IT IS ACTIVATED FROM THE
STOP
STATUS BY PRESSING THE BUTTON.
IN THIS CONDITION THE CONTROL PANEL WILL WORK ACCORDING TO THE SET APPLICATION.
STOP OPERATION:
IN THIS CONDITION THE CONTROL PANEL DOES NOT START THE MOTOR
IT SERVES TO SILENCE THE SIREN OUTPUT IN PRESENCE OF ANY ALARM
N.B.: ALL ALARMS ARE AUTOMATICALLY RESET WITH THE EXCEPTION OF THE MOTOR OVERCURRENT WHICH
RESETS BY PRESSING THE BUTTON FOR 2s
INDICATES THAT THE MOTOR IS RUNNING
INDICATES THAT THE MOTOR IS OFF
INDICATES A MOTOR OVERLOAD ALARM THAT CAUSES THE SHUTDOWN
INDICATES A MOTOR KLIXON INTERVENTION ALARM THAT CAUSES THE SHUTDOWN
SUPPLY MAINS
MISSING OR INCORRECT PHASE SEQUENCE
THE MEASURED VOLTAGE VALUE IS OUT OF THE ALLOWED THRESHOLD
LED KEY
Off
On
Flashing
<0,5s
Fast flashing