of connection due to the function of the EPO button, because 

it would not work in case of any of the two cables that goes 

from the button to the UPS were cut (damaged).
On the other hand this failure would be immediately detected  

in the normally closed EPO type, with the inconvenience of the 

sudden break in the power supply to the loads, but with a com-

plete guarantee of the functioning of the emergency power off.

•  To restore the normal operating mode of the UPS, the connector 

with the cable bridge has to be fitted back in the terminal strip 

or to deactivate the EPO button and later on to cancel the EPO 

status in the control panel . The equipment will be operative.

5.3.7.  Connection in parallel.

5.3.7.1.  Introduction to the redundancy.

N+X is usually the most reliable power structure. N means the 
minimum quantity of equipments that the total load needs; X 
means the quantity of redundant equipments, so it means, the 
quantity of faulty UPSs that the system can allow at the same 
time. As higher is X, the highest will be the reliability of the 
system. For those cases where the reliability is the most impor-
tant point, N+X will be the optimal mode.

Up to 4 equipments can be connected in parallel to set a share 
and redundant output in power.

5.3.7.2.  Installation and parallel operating.

• 

Communication line (COM) is a very low voltage circuit 

of safety. To preserve the quality, it has to be installed 

separate from other lines that have dangerous voltages (energy 

distribution line).

•  Parallel connection bus. Use the bundle with 25 signal ca-

bles with mesh and DB25 connectors in the ends to joint up 

to 4 equipments as maximum. Each bundle has a male and 

female connector in the ends, which have to be connected in 

the correlative equipments. It is essential to close the loop of 

the parallel bus.
The length of the parallel cable has 3 metres and it can't be 

extended under any other concept due to the risk of interfer-

ences and communication failures that it could cause.

• 

In those installations with only one UPS, the “Jumper” 

(cable as bridge mode) connected from factory be-

tween the terminals JP1 and JP2 has to be kept in this place.
For equipments connected in a parallel system, this “Jumper” 

has to be removed.
Proceed according to your installation or otherwise the UPS 
or parallel system will not work.

•  The installation of the parallel systems, has to be provided 

by a switchgear panel with individual protections for input, 

output, static bypass (this last one for TWIN/3 PRO > 10 kVA 

models only), also a manual bypass with mechanical lock, 

see figures 12 and 13.
This switchgear panel allows isolating only one equipment 

from the system, against any failure and feed the loads with 

the rest of equipments during the preventive maintenance or 

its fixing. In the same way, it allows removing an equipment in 

parallel and replace it or put it in parallel again once it is fixed, 

but without breaking the power supply to the loads.
Under request a manual Bypass panel can be supplied for a 
single equipment or particular system.

•  Regarding the protection panel, it is better to size it for future fore-

seen upgrading. This way, both the installation of any new UPS 

in the parallel system is easier, and the risks due to electrical dis-

charge are minimized because the low voltage panel is manoeu-

vred for those cases that it is not possible to shutdown the loads.

•  Respect the connection procedure for input and bypass 

(TWIN/3 PRO > 10 kVA) described in the previous sections 
of this chapter.

• • •

Input circuit breakers

Output circuit breakers

 M

an

ual

 B

yp

as

s

UPS nr 1

UPS nr 2

UPS nr 

"N"

Input

To loads

• • •

Fig. 12. 

Parallel installation of TWIN PRO and TWIN/3 PRO UPSs 

up to 10 kVA, with protection and manual bypass panel.

• • •

Input and bypass circuit breakers

Output circuit breakers

 M

an

ual

 B

yp

as

s        

UPS nr 1

UPS nr 2

UPS nr 

"N"

Input

To loads

• • •

Bypass line

Fig. 13. 

Parallel installation of TWIN/3 PRO series > 10 kVA, 

with manual bypass and protection panel.

Содержание UPS SLC TWIN PRO series

Страница 1: ...UNINTERRUPTIBLE POWER SUPPLY USER S MANUAL UPS SLC TWIN PRO series 4 20 kVA...

Страница 2: ......

Страница 3: ...on 5 3 9 Software 5 3 10 Considerations before starting up the connected loads 6 Operating 6 1 Commissioning 6 1 1 Controls before commissioning 6 2 Start up and shutdown of the UPS 6 2 1 Start up of...

Страница 4: ...l exclusively Although we have made every effort to guarantee a com plete and accurate information in this user s manual we are not responsible for any errors or omissions that may exist The images in...

Страница 5: ...installation and commissioning in an easy and ordered way without doubt Finally once the equipment is installed and operative for future requests or doubts that could arise it is recommended to keep...

Страница 6: ...IEC 62040 2 Uninterruptible power supply UPS Part 2 EMC requirements The manufacturers responsibility is excluded in the event of any modification or intervention in the product by the customer s sid...

Страница 7: ...due to the constant evolution of the product some discrepancies or small contradictions can arise In front of any doubt the labelling of the equipment will always prevail Figures regarding its main f...

Страница 8: ...slot EPO RS 232 USB Protection cover for external batteries IEC output connectors Protection cover for manual bypass switch maintenance and output Protection cover for power blocks USB RS 232 EPO Pro...

Страница 9: ...9 SALICRU Battery switch Protection cover for power blocks Batteries module for models 10 kVA Batteries module for models up to 10 kVA Battery switch Power blocks Fig 3 Rear view batteries module...

Страница 10: ...ith no accessories screws and electrical cables Batteries owned by the client will be installed out from the case or cabinet of the UPS Under request it is possible to supply the acces sories screws a...

Страница 11: ...low input current distortion so mains pollution is decreased Great adaptability to the worst conditions of the input mains Wide margins of the input voltage frequency range and wave shape so it is av...

Страница 12: ...adaptor The big IT systems based on LANs and WANs that integrate servers with different platforms they have to include an easy way of controlling and management at the manager system dis posal This f...

Страница 13: ...es type B for RCD devices and C characteristic for circuit breakers For the output load feeding C characteristic for circuit breaker Regarding the size they will be as minimum to the currents stated i...

Страница 14: ...o the instructions described in this manual and charge them for 12 hours In parallel systems it is not needed to make the connection among the equipments to charge the batteries It can be treated as s...

Страница 15: ...correct torque in the screws of the power blocks In installations with only one UPS the Jumper cable as bridge mode connected from factory between the terminals JP1 and JP2 has to be kept as it is Fo...

Страница 16: ...the power contactor 2 with 400V AC coil and NO contact of 5A 1A at least 4 Cable installed from factory as a bridge mode in any TWIN 3 PRO 10 kVA equipment Remove this cable fitted in as a bridge mode...

Страница 17: ...connection JP2 Output neutral N Output phase U L Output earth bonding UPS connection power block TWIN PRO UPS connection power block TWIN 3 PRO 10 kVA UPS connection power block TWIN 3 PRO up to 10 k...

Страница 18: ...the first bat tery module and from this last negative to the second module and so on Proceed in the same way to connect the red posi tive cable and the green yellow earth cable In parallel systems th...

Страница 19: ...and it can t be extended under any other concept due to the risk of interfer ences and communication failures that it could cause In those installations with only one UPS the Jumper cable as bridge mo...

Страница 20: ...ion software 5 3 8 2 Smart slot UPS s have a unique slot for TWIN PRO and two slots for TWIN 3 PRO hidden rear the covers stated in the views of the equipment One of them allows inserting the SNMP car...

Страница 21: ...h makes a user friendly interface of monitoring and management This software supplies an auto Shutdown for a system based on several PCs in case of an electrical blackout With this soft ware the end u...

Страница 22: ...will be done gradually to avoid any problem as minimum in the first commissioning If inductive loads with big inrush current apart from sensi tive ones are required to be connected like laser printers...

Страница 23: ...ck that the battery switch is in position On models B0 and B1 Turn the input M1 and bypass M2 circuit breakers to On Switch M2 is only available in models TWIN 3 PRO 10 kVA In equipments with single p...

Страница 24: ...sfer to Bypass mode Put all the equipments on manual bypass To do it re move the cover from manual bypass switch which is located at the back of each equipment and turn all the switches to position BY...

Страница 25: ...S T S Press over the shutdown key in any UPS for more than 3 seconds and each one will be shutdown supplying output voltage through the bypass Turn On the output circuit breaker switch of the distrib...

Страница 26: ...UPS and put the mechanical lock To avoid wrong manoeuvring the mechanical lock has to be fit otherwise the equipment and loads are exposed to serious damages even the de struction of both or fire Turn...

Страница 27: ...r 1 sec as minimum to validate the modified option and change the settings Table 6 Functionality of the buttons or keypad of the control panel The UPS has a control panel with the following parts Four...

Страница 28: ...s UPS only 8 20 kVA TWIN 3 Blue 81 Fault Heatsink over temperature Red Code Condition Description Color LCD 82 Alarm Ambient over temperature UPS only 4 10 kVA TWIN Blue 83 Alarm Ambient NTC abnormal...

Страница 29: ...UPS power supply information single phase input Fig 17 Main screen of the equipment with single phase input Information of load level connected to the UPS UPS power supply information three phase inpu...

Страница 30: ...ls due to fault or wrong the equipment will transfer to Battery mode to feed the load s properly Fig 24 Frequency converter mode screen This function can be activated through the settings of the contr...

Страница 31: ...beadaptedto the own needs and optimise the function of the equipment 7 3 1 Main screen From main screen when pressing the key or for less than 1 sec it is shown detailed information about the alarm pa...

Страница 32: ...UPS status menu Structure of main menu Press 1 sec Fig 31 UPS status screen Press 1 sec Press o 1 sec Structure of Data logger submenu Structure of main menu Press 1 sec Fig 32 Event logger submenu Pr...

Страница 33: ...T S password only Fig 34 Control submenu screens 7 3 5 Control submenu When pressing the key the key for less than 1 sec from this Control submenu it is accessed to the control structure see figure 34...

Страница 34: ...ation from factory 7 4 1 Operating on ECO mode 7 4 1 1 Short description of the ECO mode ECO mode function allows supplying the load s from mains directly through the internal filters only meanwhile t...

Страница 35: ...rs or service cen tres in order to avoid overheating and sparks with fire risk because the size is not enough Do not short the and poles of the batteries there is risk of fire or electrocution Be sure...

Страница 36: ...ooling and the ambient temperature of the room NTC abnormal UPS internal fault Consult with the S T S Communication cable male disconnected Para cable Male Loss Alarm code E3 Parallel bus cable is dis...

Страница 37: ...er Under Voltage Inv Under Voltage Alarm code 33 UPS internal fault Consult with the S T S Inverter Softstart Failed Inv Softstart Fail Alarm code E34 UPS internal fault Consult with the S T S Negativ...

Страница 38: ...ypothetical fault 8 3 2 Out of scope of supply Our company is not forced by the warranty if it appreciates that the defect in the product doesn t exist or it was caused by a wrong use negligence insta...

Страница 39: ...oad 2 Voltage THD with non linear load 5 Output voltage recovering time 100 ms IEC 62040 3 70 ms IEC 62040 3 60 ms IEC 62040 3 Transient response of the output voltage with load fluctuation of 0 100 0...

Страница 40: ...ending on model 273 V DC 13 65 V DC block 4 A 345 6 V DC 14 4 V DC block Floating voltage block set 13 65 V DC 273 V DC 13 65 V DC 327 6 V DC Maximum charging current 1 A 1 4 A 4 A Recharging time 5 h...

Страница 41: ...mitting Diode Circuit breaker A circuit breaker or switch is a device ready to break the electrical current of a circuit when it over comes the maximum set values On Line mode Regarding to an equipmen...

Страница 42: ...42 USER MANUAL...

Страница 43: ...43 SALICRU...

Страница 44: ...mpany salicru salicru_SA Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers The Technical Se...

Отзывы: