- 13 -
•
Over load time out
: When UPS is Over load time out, the symbol
will be displayed constantly. At the
same time, the symbol
will be displayed constantly, and the output voltage is 0Vac 0Hz.
•
Battery missing
: If the battery connection is not good, the LCD will display
“FAULT CODE 1”
.
•
Fan fail
: If the fan is locked, The symbol
“FAULT CODE 2”
will flicker every second; if the time is out. The symbol will
be displayed constantly.
•
Over temperature
: If the temperature of the UPS is too high, The LCD will display
“FAULT CODE 3”
constantly.
•
Output invalid
: If output voltage is out of range, the LCD will display
“FAULT CODE 4”
constantly.
•
Battery overcharged
: The LCD will display
“FAULT CODE 5”
constantly.
•
Output short circuit
: The LCD will display
“FAULT CODE 6”
constantly.
•
Other fault type
: The LCD will display
“FAULT CODE 8”
constantly.
13. Input type (Operation mode):
• Normal: The UPS accepts a input voltage range of ±20%.
• Generator: The low frequence transfer point changes at 40Hz and there is not limit for the high frecuence transfer point.
•
Extended margin: The UPS accepts a input voltage margin of -30% to +20%.
14. Output voltage margin:
The UPS output voltage selection:110Vac/120Vac/127Vac o 220Vac/230Vac/240Vac.
110Vac/120Vac/127Vac are LV mode (low voltage).
220Vac/230Vac/240Vac are HV mode (high voltage).
Example: To a HV UPS, after selection the 230Vac mode (default selection) by the switchs "CNFG" and "ENTER", the
output voltage will be approximately 230V, and the LCD display will be how the next figure shows:
Содержание UNINTERRUPTIBLE POWER SUPPLY ADVANCE series
Страница 1: ...EK459B01 User s manual installation and start up UNINTERRUPTIBLE POWER SUPPLY ADVANCE series...
Страница 2: ...2...
Страница 14: ...14 Examples to the LCD display If the mains supply exist If the mains supply do not exist...
Страница 15: ...15 4 2 Introducing the LCD display 4 3 Audible alarm introduction polarity...
Страница 19: ...19 Rear panel for LV model Rear panel description for LV and HV models table SNMPSlot orAS400 SNMPSlot orAS400...
Страница 36: ...36 9 TROUBLE SHOOTING 9 1 Audible Alarm Trouble Shooting 9 2 General Trouble Shooting...
Страница 37: ...37 10 SPECIFICATION Optocouplers 10 5 21 5 N A N A...
Страница 39: ...39...
Страница 40: ...salicru com 08460Palautordera Tel 3493 8482400 sat salicru com...