• Do not place materials on the unit or elements that might prevent the front from being seen.

• Set up the unit as close as possible to the socket and to the loads to be supplied.

• In cleaning the units, do not use abrasive or corrosive products, liquids or detergents. If you wish to clean the unit,

pass a damp cloth and dry immediately. Avoid splashing or spilling, which might enter slots or ventilation grilles.

• In order to prevent the batteries from discharging completely, and as a safety measure after a long cut in the mains

supply and at the end of the working day, the loads must be shut down, followed by the unit, following the
operation described in the "Instructions Manual ".

• When a fuse has to be replaced, the replacement will be of the same calibre, type and size.

3.2.-

 General warnings.

• The 

UPS

 is a continuous supply unit. If the supply mains disappears when it is running, the output lines still have

voltage, depending on the autonomy given by the battery unit.

• All connections will be performed without mains supply present and with the unit idling.

• The cross sections of the cables used to supply the unit and the loads to be supplied will be in line with the nominal

current indicated on the characteristics plate and adhered to the unit, respecting the Low Voltage Electrotechnical
regulation.

• Pay special attention to the labelling of the unit that warns of the "Danger of electrical discharge " and indicated

as (

). There are dangerous voltages inside the unit: never open the case, access must only be made by

authorised, competent personnel. In the event of maintenance of breakdown, consult your closest After Sales
Service (

A.S.S.

).

• The protective ground connection must be made, and always before the input voltage is connected. For small

apparatuses (connected with the cable supplied with a socket pin), users must ensure that the current socket
corresponds to the type supplied, with the ground duly installed and connected to the local protection ground.
For units with terminals, the installer must connect the ground line to the terminal indicated as ( ).

• All electric cables supplying the units and the loads must be fixed to non moving parts to prevent them from being pulled.

• It must be considered that if the unit has a Bypass, with the mains present it will supply voltage to the output

without necessarily being running: Place warning signs and/or emergency switches if the safety regulations of your
specific installation so require.

• RACK-mounted products are intended for installation in a predetermined unit set up by professionals. Their

installation must be planned and carried out by qualified personnel, who will be responsible for applying the
legislation and safety and EMC regulations covering the specific installations in which the product is to be used.

• The batteries generally come as part of the unit, but are exceptionally supplied in an independent case. For the

unit to work optimally, both elements must be placed as closely as possible together without extending the cables
supplied.

Содержание NX Series

Страница 1: ...NX UNINTERRUPTIBLE POWER SUPPLY series NX SYST ME D ALIMENTATION SANS INTERRUPTION s rie NX Manual de usuario instalaci n y puesta en marcha User s manual installation and start up Manuel d utilisate...

Страница 2: ...URIDAD 6 SAFETY WARNINGS 20 MISES EN GARDE DE S CURIT 34 Manual de usuario instalaci n y puesta en marcha 5 18 User s manual installation and start up 19 32 Manuel d utilisateur installation et mise e...

Страница 3: ...your entire disposal for any further information or any query you should wish to make Thank you In our policy of constant evolution we reserve the right to modify the characterisitcs in part or in who...

Страница 4: ...4...

Страница 5: ...r de polaridad de entrada P 6 2 Conexi n de la salida Conexi n con las cargas a alimentar 6 3 Conexi n con las bater as externas conector 4 6 4 Conexi n interface a optoacopladores y RS 232 6 5 Softwa...

Страница 6: ...tes Las instrucciones e ilustraciones de este manual son gen ricas para toda la serie y son una gu a como referencia Si su modelo no equipa alguno de los elementos descritos omitir toda referencia y p...

Страница 7: ...autorizado y competente En caso de mantenimiento o aver a consultar al SAT m s pr ximo Debe conectarse obligatoriamente la conexi n de tierra de protecci n asegur ndose que ello se realiza antes de co...

Страница 8: ...nerse una bater a a altas temperaturas Existe peligro de explosi n No romper la carcasa ni intentar abrirla El electr lito interior es t xico y da ino para la piel y ojos En caso de contacto del cido...

Страница 9: ...ise ados a alta frecuencia PWM y sin transformador de tama o muy compacto y adecuado para cualquier aplicaci n donde se requiera alimentar equipos electr nicos Como protecci n propia el SAI conmutar a...

Страница 10: ...u embalaje original ya que ha sido espec ficamente dise ado para asegurar al m ximo la protecci n durante el transporte y almacenaje El SAI incorpora bater as herm ticas de plomo calcio salvo casos pa...

Страница 11: ...Si bajo estas condiciones el led de l nea a se ilumina significa que la polaridad de red en la clavija 1 es correcta si por el contrario permanece apagado es signo de polaridad erronea Desconectar la...

Страница 12: ...n funcionamiento Nota La conexi n del interface entre el SAI y el ordenador no es impl cita en cuanto al funcionamiento de ambos equipos se refiere En caso de realizar la conexi n use nicamente el cab...

Страница 13: ...as a posici n ON si el equipo dispone de autonom a extendida Aplicar tensi n de red comercial a la entrada del SAI Desde el momento que se ha aplicado la tensi n de red comercial y el fusible o magne...

Страница 14: ...de unos 15 segundos se transferir la carga sobre el inversor 7 4 Funci n auto test Utilice el auto test tanto para verificar el funcionamiento correcto del SAI como el de las condiciones de las bater...

Страница 15: ...zca la sobrecarga En caso de cortocircuito se dispara el fusible o magnetot rmico 5 y transfiere sobre inversor modo autonom a quien a su vez realiza un Shutdown de la salida Sobrecarga inversor en mo...

Страница 16: ...arga Pulsar la tecla 6 On durante 1 seg la alarma de Descarga se inhibir No es posible silenciar cualquiera de las otras alarmas 9 LOCALIZACI N DE FALLOS Ver tabla 1 10 CARACTER STICAS T CNICAS Entrad...

Страница 17: ...do Polaridad clavija de entrada 1 incorrecta Pulsador 6 sin activar o presionado duran te poco tiempo Tensi n bater as baja Fallo unidad electr nica de potencia Cortocircuito o sobrecarga en la salida...

Страница 18: ...do CE Calidad ISO 9001 Tabla 2 Caracter sticas t cnicas particulares Modelo Potencia Autonom a a Dimensiones Peso neto VA W media carga min Fondo x ancho x alto mm kg UPS 700 NX 700 490 15 400 x 145 x...

Страница 19: ...Input polarity detector P 6 2 Connection of the output Connection to the loads to be supplied 6 3 Connecting to external batteries connector 4 6 4 Connection interface to optocouplers and RS 232 6 5 S...

Страница 20: ...in the manual Where discrepancies occur users must comply with all pertinent local regulations The instructions and illustrations in this manual are generic for the whole series and are a guide for re...

Страница 21: ...e and indicated as There are dangerous voltages inside the unit never open the case access must only be made by authorised competent personnel In the event of maintenance of breakdown consult your clo...

Страница 22: ...high temperatures for risk of explosion Do not break the housing or attempt to open it The internal electrolyte is toxic and harmful to skin and eyes In the event of acid coming into contact with par...

Страница 23: ...charge automatically when the unit is simply connected to the mains regardless of whether the UPS is running These UPS are designed at high frequency PWM without transformer and are very compact and s...

Страница 24: ...al agents It is best to keep the unit in their original packing as this packing has been specifically designed to ensure maximum protection during transport and storage The UPS includes sealed lead ca...

Страница 25: ...ditions the line LED a lights up it means that the network polarity in the plug 1 is correct If on the other hand it does not light up this is a sign that the polarity is wrong Disconnect the plug 1 f...

Страница 26: ...pplied when the whole installation is working Note The connection of the interface between the UPS and the computer is not implicit to the working of both units In the event of making the connection u...

Страница 27: ...has extended autonomy Apply mains voltage to the input of the UPS From the very moment that the mains voltage has been applied and the corresponding fuse or the circuit breaker 5 has been either fitte...

Страница 28: ...eep will sound and after some 15 seconds the load will be transferred on the inverter 7 4 Self test function Use the self test to check the correct performance of the UPS as well as the conditions of...

Страница 29: ...ss mode until the overload disappears In the event of a short circuit the fuse or switch 5 will trip and it will transfer over the inverter in autonomy mode which in turn will effect a shutdown at the...

Страница 30: ...a turned off an audible modulated alarm is activated Press the ON key 6 for 1 second the Discharge alarm will be inhibited It is not possible to silence any of the other alarms 9 FAULT LOCALISATION Se...

Страница 31: ...anent alarm Red Led g light Incorrect input plug 1 polarity Pushbutton 6 not activated or pressed for too short a time Low battery voltage Failure of the electronic power unit Short circuit or overloa...

Страница 32: ...000 NX 2000 1400 25 460 x 192 x 385 28 1 UPS 2000 NX R 2000 1400 25 470 x 483 x 130 27 UPS 3000 NX 3000 2100 20 460 x 192 x 385 33 3 UPS 3000 NX R 3000 2100 20 470 x 483 x 130 31 Communications Interf...

Страница 33: ...entr e P 6 2 Connexion de la sortie connexion avec les charges alimenter 6 3 Connexion aux batteries externes connecteur 4 6 4 Connexion interface optocoupleurs et RS 232 6 5 Logiciel 6 5 1 Structure...

Страница 34: ...ructions et les illustrations de ce manuel sont g n riques pour toute la s rie et servent de guide de r f rence Si votre mod le n est pas accoupl l un des l ments d crits omettez la r f rence et conti...

Страница 35: ...aintenance ou de panne consultez le SAT le plus proche Branchez le obligatoirement une prise de terre de protection et assurez vous de l avoir fait avant de brancher la tension d entr e Pour les petit...

Страница 36: ...atterie des temp ratures lev es car il y a risque d explosion Ne cassez pas la carcasse n essayez pas de l ouvrir L lectrolyte int rieur est toxique et nocif pour la peau et les yeux En cas de contact...

Страница 37: ...ries se rechargent automatiquement pour la simple raison que l appareil est raccord au r seau ind pendamment du fait que l ASI soit en marche ou non Ces ASI sont con us pour travailler en haute fr que...

Страница 38: ...erver l appareil dans son emballage d origine car il est sp cialement con u pour assurer la protection maximale pendant le transport et le stockage L ASI contient des batteries herm tiques en plomb ca...

Страница 39: ...teries Si dans ces conditions le led de ligne a s allume cela signifie que la polarit de r seau la fiche 1 est correcte Si par contre il reste teint le signe de polarit est incorrect D connecter la fi...

Страница 40: ...arche Remarque Le branchement de l interface entre le ASI et l ordinateur n est pas implicite en ce qui concerne le fonctionnement des deux appareils Pour les brancher utilisez seulement le c ble four...

Страница 41: ...si l appareil dispose d une autonomie prolong e Appliquez la tension du r seau commercial l entr e du ASI D s que la tension du r seau commercial est apploqu e et que le fusible ou le magn tothermique...

Страница 42: ...ps et les maintenir enfonc es pendant 5 secondes environ Un signal sonore retentira et au bout de 15 secondes la charge sera transf r e sur l inverseur 7 4 Fonction autotest Utilisez autotest pour v r...

Страница 43: ...que la surcharge disparaisse En cas de court circuit le fusible ou magn tothermique 5 se d clenche et passe sur inverseur mode autonomie qui son tour r alise un Shutdown de la sortie Surcharge inverse...

Страница 44: ...c allum et alarme acoustique d clench e appuyez sur le bouton 6 pendant 1 seconde et l alarme s arr tera Il est impossible de d sactiver l alarme acoustique de Batterie faible fin d autonomie ou Surc...

Страница 45: ...incorrecte Bouton 6 non activ ou enclench trop vite Tension batteries faible Panne unit lectronique de puissance Court circuit ou surcharge la sortie du ASI C ble entr e d branch D clenchement du fusi...

Страница 46: ...1400 25 460 x 192 x 385 28 1 UPS 2000 NX R 2000 1400 25 470 x 483 x 130 27 UPS 3000 NX 3000 2100 20 460 x 192 x 385 33 3 UPS 3000 NX R 3000 2100 20 470 x 483 x 130 31 Communication Interface optocoup...

Страница 47: ...47...

Страница 48: ...48 Fig 6 Frontal Front Vue avant UPS NX R Rack 1 Fig 7 2 UPS 700 NX UPS 1500 NX UPS 2000 NX UPS 3000 NX Fig 5 Frontal Front Vue avant UPS NX 1 Fig 7 1 1 Fig 7 1...

Страница 49: ...49 Fig 7 2 d h f b e a g c 6 7 Fig 7 1 h 6 a 7 b d e g f c a...

Страница 50: ...50 Fig 8 1 Posterior Rear Vue arri re UPS 700 NX UPS 1500 NX 3 5 1 4 0 2 8 Fig 8 2 Posterior Rear Vue arri re UPS 2000 NX UPS 3000 NX 3 4 2 5 0 8 1...

Страница 51: ...51 Fig 9 2 Posterior Rear Vue arri re UPS 2000 NX R UPS 3000 NX R Rack 8 2 3 1 4 0 5 Fig 9 1 Posterior Rear Vue arri re UPS 700 NX R UPS 1500 NX R Rack 8 2 3 1 4 0 5...

Страница 52: ...salicru com 08460Palautordera Tel 34938482400 sat salicru com...

Отзывы: