Salicru EQUINOX2 3001-S Скачать руководство пользователя страница 58

58

SALICRU

e. 

Connect the AC connector to the inverter's AC terminal; 

a click indicates that the connection is in place, as shown 

in Fig. 31:

Fig. 31.  Connecting the AC connector to the inverter's AC terminal.

f. 

Insert the relevant AC circuit breakers in between, 

as shown in the table below:

Model

Thermal-

magnetic 

circuit 

breaker

Differen-

tial relay

Over-

voltage 

protection

Previous 

fuse. Max. 

value 

(1/phase)

EQX2 2001-S

2P 16A 

Curve C

2P 25A 

30mA 

Class A 

40kA 230V 

TT Type II

125 A gL

EQX2 3001-S

2P 20A 

Curve C

EQX2 3002-S
EQX2 3002-SX
EQX2 4002-S

2P 32A 

Curve C

2P 40A 

30mA 

Class A

EQX2 4002-SX
EQX2 5002-S

2P 40A 

Curve C

EQX2 5002-SX
EQX2 6002-S
EQX2 6002-SX

EQX2 8002-SX

2P 50A 

Curve C

2P 63A 

30mA 

Class A

EQX2 10002-SX

2P 63A 

Curve C

Tab. 10. AC circuit breakers

g. 

Connect the other end of the hose to the AC circuit breaker 

in the junction box, downstream of the connection's IGA.

L

N

Fus.

SPD

IGA

GND

MCB

Inverter

ID

ID

PIAs

Fig. 32.  Electrical wiring diagram. 

For the connection of equipment with 24h monitoring, see 

manual EL23300.

Содержание EQUINOX2 3001-S

Страница 1: ...EQX2 3001 S EQX2 3002 S EQX2 3002 SX EQX2 4002 S EQX2 4002 SX EQX2 5002 S EQX2 5002 SX EQX2 6002 S EQX2 6002 SX EQX2 8002 SX EQX2 10002 SX ES EN MANUAL DE USUARIO INVERSORES SOLARES MONOF SICOS DE CON...

Страница 2: ...2 SALICRU...

Страница 3: ...5 3 1 Diagrama de conexionado general 5 3 2 Conexi n a tierra externa 5 3 3 Conexi n del panel fotovoltaico 5 3 4 Conexi n de la salida AC 5 4 INSTALACI N DEL DISPOSITIVO DE MONITORIZACI N 5 4 1 Inst...

Страница 4: ...ar de que no se han escatimado esfuerzos para garan tizar que la informaci n de este manual de usuario sea com pleta y precisa no nos hacemos responsables de los errores u omisiones que pudieran exist...

Страница 5: ...sobre la misma persona la responsabilidad de realizar las respectivas acciones al actuar en nombre o representaci n del mismo 3 2 NOTAS DE SEGURIDAD 1 Antes de la instalaci n leer con atenci n este ma...

Страница 6: ...ones antes de la instalaci n No toque ninguna parte interna del inversor hasta 5 minutos despu s de haber sido desconectado de la red y de la entrada fotovoltaica Marca CE el inversor cumple con los r...

Страница 7: ...e potencia utilizados en sistemas de potencia fotovoltaicos Parte 2 Requisitos particulares para inversores Compatibilidad electromagn tica IEC EN UNE 61000 6 2 2005 Compatibilidad electromag n tica C...

Страница 8: ...o No h brido Potencia redondeada en W n mero MPPT Nombre serie 5 1 4 Reg menes de neutro aplicables Los reg menes de neutro aplicables para la serie EQX2 son TN S TN C TN C S y TT Cuando se aplica a l...

Страница 9: ...EQX2 4002 S EQX2 4002 SX EQX2 5002 S EQX2 5002 SX EQX2 6002 S EQX2 6002 SX EQX2 8002 SX y EQX2 10002 SX 360 mm 410 mm Logo Display Fig 6 Vista frontal 120 mm 360 mm Placa de caracter sticas Fig 7 Vist...

Страница 10: ...ambia la informaci n de la pantalla OLED y configura los par metros mediante presi n breve y presi n prolongada ver cap tulo 7 Operaci n del sistema Indicador de alarma On Lacomunicaci nentreelinverso...

Страница 11: ...pines ubicado en el mismo conector del equipo 2 5 Conectores PV 6 Antena WiFi para monitorizaci n de 12h Funciona nicamente para redes de 2 4 GHz 1 7 Conector AC y llave tipo Allen 1 8 Terminal Tierr...

Страница 12: ...stalaci n La ubicaci n recomendada para los inversores es en inte riores No obstante si no hay m s remedio que realizar la instalaci n en el exterior la Fig 13 muestra las ubicaciones reco mendadas as...

Страница 13: ...ectados a la misma barra de cobre de puesta a tierra para garantizar la conexi n equipotencial Pasos para la conexi n del terminal a tierra 1 Elterminaldeconexi natierraexternaest ubicadaenellado infe...

Страница 14: ...et lico y presionar el terminal con unos alicates profesionales de prensado tirar del cable para verificar si el terminal est bien conectado al cable tal como se muestra en la Fig 19 Para asegurar una...

Страница 15: ...nesconun nico campo solar paneles en la misma orienta ci n y strings de igual longitud Fus PV SPD MCB Inversor Fig 22 Conexi n nico campo solar 1 string y 1 MPPT MCB MCB Fus Fus SPD SPD PV PV Inversor...

Страница 16: ...distintos campos solares y 2 MPPT Se entiende por campo solar distinto a aquellos que est n formados por paneles de distintos fabricantes longi tudes y o potencias distintas 4 Inserte los conectores...

Страница 17: ...erte la pieza pl stica en los orificios marcados en rojo y tire del cabezal del conector El conector AC completamente desmontado se muestra a continuaci n Prensa estopas Manga roscada Cabezal terminal...

Страница 18: ...2P 25A 30mA Clase A Tipo II 40kA 230V TT 125 A gL EQX2 3001 S 2P 20A Curva C EQX2 3002 S EQX2 3002 SX EQX2 4002 S 2P 32A Curva C 2P 40A 30mA Clase A EQX2 4002 SX EQX2 5002 S 2P 40A Curva C EQX2 5002 S...

Страница 19: ...l en el siguiente orden tap n de rosca anillo de sellado aislante placa de metal tuerca y conector de 3 6 pines tal como se muestra en la Fig 35 Conector 3 pin Anillo aislamiento Tuerca Tap n de rosca...

Страница 20: ...izadopararepresentarlareddedistribuci n NEGRO MARR N o GRIS para las fases L1 L2 y L3 y AZUL para el neutro C digo de colores utilizado para representar la alimentaci n de AC de la instalaci n MARR N...

Страница 21: ...trar en el modo de generaci n AC DC 4 El equipo se pondr en marcha La pantalla LCD se encender En el siguiente apartado se detallan los pasos a seguir y el fun cionamiento de la consola Seguir los sig...

Страница 22: ...namiento des de su puesta en marcha 10 Men pantalla Modelo Equipo Pantalla 9 1 Indicador del c digo del equipo 11 Men pantalla Config general Pantalla 10 1 Pantalla principal del men de Config general...

Страница 23: ...os horizontalmente por el men Si dentro de un men no pulsamos ninguna tecla durante m s de 10 segundos volveremos autom ticamente al men prece dente E D a E Total Tiempo ON Modelo Equipo Pantalla 6 1...

Страница 24: ...0549 Hr France 50Hz 50Hz default India EN50549 Cz EN50549 Se Belgium France 60Hz 60Hz default Philippines EN50549 Tr EN50549 Pl Fra mainland VDE0126 VDE4105 Vietnam IEC 50 Hz Seguridad UNE 217002 Pant...

Страница 25: ...do conforme al apartado 5 5 3 8 4 MONITORIZACI N ON LINE DE LA INSTALACI N El inversor EQX2 proporciona un puerto de supervisi n que puede recopilar y transmitir datos desde el inversor a la plataform...

Страница 26: ...mensaje se encuentra un c digo Token de6d gitos Introducirelc digoenlapantalladecom probaci n del c digo y pulsar enviar 5 6 Aparecer una pantalla para introducir una contrase a nueva Es necesario int...

Страница 27: ...creado la planta correctamente mediante un mensaje en la parte inferior y apare cer una nueva cabecera en el panel de Mis plantas 8 4 3 Monitorizaci n 12h D a Este modo de monitorizaci n funciona nica...

Страница 28: ...r a sus detalles Por ahora nicamente se mostrar la potencia del campo solar que se haya introducido porqu los instrumentos de medida a n no est n conectados y se indica con el mensaje de Dispositivos...

Страница 29: ...est conectado al equipo en el puerto USB b Pulsar el bot n Siguiente 2 A adir dispositivo Para a adir el equipo a la planta de debe vincular el n mero de serie del inversor a Pulsar el bot n de Escan...

Страница 30: ...se a ada correctamente Se indica con el siguiente mensaje Segunda Que el dispositivo que se intenta a adir ya est dado de alta Se indica con el siguiente mensaje 3 Conexi n del dispositivo Una vez vin...

Страница 31: ...as instalaciones ir n apareciendo en la lista ordenadas alfab ticamente Informaci n que proporciona la cabecera de la planta Nombre de la planta Ubicaci n de la planta La producci n durante el d a de...

Страница 32: ...or por lo que los 2 05 kW sobrantes se inyectan a la red como excedentes En caso de no tener consumo el diagrama sin ptico lo mostrar a de la siguiente manera En la secci n de Generaci n se pueden vis...

Страница 33: ...incluso tener una idea de la degradaci n de los paneles En la secci n de Ahorro econ mico se grafican los valores aproximados de Ahorro por generaci n importe que se obtiene multiplicando la generaci...

Страница 34: ...de tierra fiable Fallo CFGI Corriente de fuga excesiva La corriente de tierra es demasiado alta Comprobar si el cable fotovoltaico est cortocircuitado a tierra Sobretensi n fotovoltaica Tensi n del s...

Страница 35: ...perfectamentesinnecesidad de estar conectado a internet Adem s los datos m s relevantes de generaci n se pueden observar en el display del propio equipo La nica funci n de la antena WiFi es la de pro...

Страница 36: ...3300 4600 5500 6600 8800 11000 Tensi n nominal V 220 230 Frecuencia nominal Hz 50 60 45 55 55 65 50 60 Corriente nominal AC A 8 7 13 18 3 21 7 26 1 34 8 43 5 Corriente m x AC A 14 4 15 21 25 28 7 38...

Страница 37: ...itud m xima m 3000 Enfriamiento Convecci n natural Nivel de ruido dB 25 Display OLED LED Comunicaci n RS485 WiFi Opcional Normativa NB T32004 IEC62109 IEC62116 VDE4105 VDE0126 UTE C15 712 1 AS4777 C10...

Страница 38: ...do de usuario 3 Se entrar en la interfaz System Ver Fig 43 1 Los corresponden a los ltimos 8 d gitos del SN del Inversor Fig 43 Interfaz System 4 Hacer clic en STA Setting para entrar en la Interfaz d...

Страница 39: ...r clic en Save Ver Fig 48 SSID_router_instalacion Fig 48 Pantalla guardar password 8 El sistema mostrar le mensaje Saved Successfully hacer click en Restart para completar la configuraci n de la WiFi...

Страница 40: ...maci n sobre la garant a est disponible en nuestro sitio web www salicru com Gama de Productos Sistemas de Alimentaci n Ininterrumpida SAI UPS Variadores de Frecuencia Fuentes de Alimentaci n Ondulado...

Страница 41: ...1 S EQX2 3001 S EQX2 3002 S EQX2 3002 SX EQX2 4002 S EQX2 4002 SX EQX2 5002 S EQX2 5002 SX EQX2 6002 S EQX2 6002 SX EQX2 8002 SX EQX2 10002 SX EN USER MANUAL SINGLE PHASE SOLAR INVERTERS CONNECTED TO...

Страница 42: ...42 SALICRU...

Страница 43: ...5 3 1 External earthing connection 5 3 2 Photovoltaic panel connection 5 3 3 Connecting the AC outlet 5 4 INSTALLATION OF THE MONITORING DEVICE 5 4 1 Mechanical installation 5 5 CT RS485 CONNECTION 5...

Страница 44: ...antee that the information in this user manual is complete and accurate we are not responsible for any errors or omissions that may be present The images included in this document are for illustrative...

Страница 45: ...carry out the corresponding actions whereby the responsibility for carrying out the respective actions may be held by the same person when they act on behalf or in representation of the installer or o...

Страница 46: ...before installation Do not touch any internal part of the inverter for 5 minutes after it has been disconnected from the grid and from the photovoltaic input CE marking the inverter meets the require...

Страница 47: ...ower converters for use in photovoltaic power systems Part 2 Particular requirements for inverters Electromagnetic compatibility IEC EN UNE61000 6 2 2005 Electromagneticcompatibility EMC Part 6 2 Gene...

Страница 48: ...15 A MPPT T Three phase H Hybrid Non hybrid Rounded power in W MPPT number Serial name 4 1 4 Applicable neutral points The applicable neutral points for the models of the EQX2 series are TN S TN C TN...

Страница 49: ...EQX2 3002 SX EQX2 4002 S EQX2 4002 SX EQX 5002 S EQX2 5002 SX EQX2 6002 S EQX2 6002 SX EQX2 8002 SX y EQX2 10002 SX 360 mm 410 mm Logo Display Fig 6 Front view 120 mm 360 mm Nameplate Fig 7 Side view...

Страница 50: ...rmation on the OLED screen and set the parameters with a short press and long press see 7 System operation Alarm indicator On The communication between the inverter and the server is normal However th...

Страница 51: ...ing bracket 1 3 Expansion bolts 4 4 3 pin connector located in the same connector of the equipment 2 5 PV connectors 6 WiFi antenna for 12h monitoring It works only for 2 4 GHz networks 1 7 AC connect...

Страница 52: ...out of the reach of children 5 1 1 Installation location We recommend installing inverters indoors However if there is no choice but to install outdoors shows recommended locations as well as those t...

Страница 53: ...ctedtothesamecopperearthing bar to ensure equipotential bonding Steps for connecting the terminal to earth 1 The external earthing connection terminal is located on the lower right side of the inverte...

Страница 54: ...the DC cable through the DC connector nut on the metal terminal and press the terminal with professional crimping pliers pull the cable to check if the terminal is well connected to the cable as shown...

Страница 55: ...s with a single solar field panels in the same direction and strings of equal length Fus PV SPD MCB Inverter Fig 22 Single solar field connection 1 string and 1 MPPT MCB MCB Fus Fus SPD SPD PV PV Inve...

Страница 56: ...24 Connection of several solar fields and 2 MPPTs A different solar field is understood to be those that are made up of panels from different manufacturers lengths and or different powers 4 Insert the...

Страница 57: ...astic piece into the holes marked in red and pull the connector head out The fully disassembled AC connector is shown below Cable gland Threaded sleeve AC terminal head Fig 27 AC connector b According...

Страница 58: ...01 S 2P 16A Curve C 2P 25A 30mA Class A 40kA 230V TT Type II 125 A gL EQX2 3001 S 2P 20A Curve C EQX2 3002 S EQX2 3002 SX EQX2 4002 S 2P 32A Curve C 2P 40A 30mA Class A EQX2 4002 SX EQX2 5002 S 2P 40A...

Страница 59: ...ole and connect it to the terminal in the following order screw cap sealing ring insulator metal plate nut and 3 6 pin connector as shown in Fig 35 3 pin connector Insulator ring Nut Screw cap Metal p...

Страница 60: ...ads Port 2 DC PV Protections AC Protections RED BLACK Port 1 Connection point Meter Fig 37 Inverter installation diagram Color code used to represent the distribution network BLACK BROWN or GRAY for p...

Страница 61: ...ate the generation mode AC DC 4 The unit will start The LCD screen will turn on The next section describes the steps that must be followed and the operation of the console Follow the steps below to st...

Страница 62: ...of the time that the inverter has been in operation since its start up 10 Unit Model screen menu Screen 9 1 Unit code indicator 11 General Settings screen menu Screen 10 1 Main screen of the General...

Страница 63: ...menu If no key is pressed for more than 10 seconds in a menu the system will automatically return to the previous menu E Day E Total Time ON Unit model Screen 6 1 Screen 7 1 Screen 8 1 Screen 9 1 Scre...

Страница 64: ...r France 50 Hz 50 Hz default India EN50549 Cz EN50549 Se Belgium France 60 Hz 60 Hz default Philippines EN50549 Tr EN50549 Pl Fra mainland VDE0126 VDE4105 Vietnam IEC 50 Hz Safety UNE 217002 Screen 10...

Страница 65: ...The EQX2 inverter provides a monitoring port that can gather and transmit data from the inverter to the monitoring platform through an external monitoring device There are two methods available via d...

Страница 66: ...to that email address 5 The message will include a 6 digit Token code Enter the code on the code verification screen and press submit 5 6 A screen will appear to enter a new password You need to ente...

Страница 67: ...ant has been successfully created by means of a message at the bottom and a new header will appear in the My plants panel 7 4 3 12h Monitoring Day This monitoring mode only works during the hours of s...

Страница 68: ...access its details For the time being only the power of the solar field that has been entered will be displayed because the measurement instruments are not yet connected this will be shown with the D...

Страница 69: ...ugged into the unit s USB port b Press the Next button 2 Add device You must link the inverter s serial number to add the unit to the plant a Press the Scan button The smartphone or tablet may request...

Страница 70: ...ully This is indicated with the following message 2 The device you are trying to add is already registered This is indicated with the following message 3 Device connection Once the dongle has been pai...

Страница 71: ...ther installations are created in the future they will appear in the list in alphabetical order Information provided by the plant header Plant name Plant location Today s production The date and time...

Страница 72: ...umed of which 2 74 kW are being generated by the inverter so the remaining 2 05 kW is inject into the grid as excess power If there is no consumption the synoptic chart would show this as follows The...

Страница 73: ...an idea of the degradation of the panels The Economic savings section shows charts with the approximate values of Savings per generation amount obtained by multiplying the generation by the price of...

Страница 74: ...ection CFGI error Excessive leakage current Excessively high earth current Check the photovoltaic cable to see if it is short circuited to earth Photovoltaic overvoltage The voltage of the photovoltai...

Страница 75: ...uld this pose a problem The inverter will work perfectly since it does not need to be connected to the Internet In addition the most relevant generation data are shown on the unit s display The WiFi a...

Страница 76: ...parent power AC 3300 4600 5500 6600 8800 11000 Rated voltage V 220 230 Rated frequency Hz 50 60 45 55 55 65 50 60 Rated AC current A 8 7 13 18 3 21 7 26 1 34 8 43 5 Max AC current A 14 4 15 21 25 28 7...

Страница 77: ...2 SX Maximum altitude m 3000 Cooling Natural convection Noise level dB 25 Display OLED LED Communication RS485 WiFi Optional Standards NB T32004 IEC62109 IEC62116 VDE4105 VDE0126 UTE C15 712 1 AS4777...

Страница 78: ...gin 3 The System interface will open See Fig 31 1 The correspond to the last 8 digits of the inverter s S N Fig 43 Interface system 4 Click on STA Setting to open the Interface Wi Fi setup If this is...

Страница 79: ...click on Save See Fig 46 SSID_router_installation Fig 48 Save password screen 8 The system will show the message Saved Successfully Click on Restart to complete the WiFi setup See Fig 47 Fig 49 WiFi...

Страница 80: ...80 SALICRU...

Страница 81: ...81 ES EQX2 INVERSORES SOLARES DE CONEXI N A RED MANUAL DE USUARIO...

Страница 82: ...e network TSS the sales network and the warranty is available on our website www salicru com Product range Uninterruptible Power Supplies UPS Variable Frequency Drives VFDs Power supplies Static inver...

Отзывы: