Salicru BM-R 10 Скачать руководство пользователя страница 10

10

SALICRU

To the AC wall inlet.

From IEC UPS or stabilizer 

output connector 

IEC outlets to loads

To IEC UPS or stabilizer 

input connector

Fig. 7. 

Example of 3 kVA manual bypass wiring.

 

For 6 and 10 kVA models, the manual bypass has an aux-

iliary contact 

10

 labelled as EBMS, which has to be con-

nected with its homologous located in the UPS or stabilizer, 

where its mission has been previously described.

The risk of short-circuit is increased in case of 

wrong manoeuvring, when the UPS or stabilizer do 

not have this contact or it has not been connected. Make 

the steps following the stated order.

 

Illustrations of Fig. 7 and/or 8 show how to connect the 

manual bypass with a UPS or stabiliser and loads, de-

pending on its power rate.

Respect the stated input and output strictly, other-

wise the UPS or stabiliser, manual bypass and loads 

can be damaged.

 

As this is an equipment with protection against 

electrical shocks class I, it is essential to install the 

main earth protection cable 

[

]

.

 

ˆ

In 3 kVA bypass models.

The bypass power supply plug will be connected to a 

wall outlet with protection earth duly installed, which 

through the IEC connectors will be connected to the en-

tire system.

 

ˆ

In 6 and 10 kVA bypass models.

Connect the main earth protection cable 

5

 to the ter-

minal 

[

]

. There is a second terminal 

5

 beside the 

output terminals. The earth protection cable to be con-

nected to the UPS or stabilizer can be taken from any 

of them.

1

N

1

R

4

U

4

N

3

U

3

N

2

R

2

N

Bypass

 

signal

To an AC wall outlet or 

grid terminals.

To UPS or stabilizer 

input.

From UPS or stabilizer 

output.

Fig. 8. 

Example of 6 an 10 kVA manual bypass wiring.

Содержание BM-R 10

Страница 1: ...USER S MANUAL RACK MOUNTING MANUAL BYPASS BM R 3 6 and 10 kVA...

Страница 2: ...2 SALICRU...

Страница 3: ...and contents 6 2 LOCATION AND CONSIDERATIONS 6 2 1 1 Location 6 3 WIRING 7 OPERATING 7 1 START UP 7 2 TRANSFERENCE FROM NORMAL OR UPS MODE TO BYPASS 7 2 1 3 kVA manual bypass models from NORMAL to BYP...

Страница 4: ...ed personnel Although no effort has been spared to ensure that the information in this user manual is complete and accurate we are not responsible for any errors or omissions that may exist The images...

Страница 5: ...rms are used interchangeably in the document to refer to Manual bypass Bypass equipment or unit Rack mounting manual bypass T S S Technical Service and Support Client installer operator or user These...

Страница 6: ...ercialized in accordance with the standard EN ISO 9001 of Quality Management Systems and certified by SGS body The marking shows the conformity to the EEC Directive by means of the application of the...

Страница 7: ...y IEC connector or input terminals 2 To be connected to the UPS or stabilizer input 3 To be connected to the UPS or stabilizer output 4 IEC connectors or output terminals to loads 5 Main protective ea...

Страница 8: ...onnection with the sup plied cable between this connector and the one available in several equipments like the UPS from TWIN PRO2 and or RT2 series when the protecting cover from manual bypass is remo...

Страница 9: ...TION AND CONSIDERATIONS 6 2 1 1 Location Remove the angles and screws from the plastic bag and assemble them on the rack mounting bypass These devices are designed to be integrated into rack cabinets...

Страница 10: ...ing on its power rate Respect the stated input and output strictly other wise the UPS or stabiliser manual bypass and loads can be damaged As this is an equipment with protection against electrical sh...

Страница 11: ...the UPS or stabilizer have not been transferred to Bypass mode when the protection cover 13 is removed the equipment will shift to this operating mode automati cally provided that the bypass signal 10...

Страница 12: ...fix an hypothetical failure the procedure formality will be smoother 8 2 2 Out of scope of supply In case it is detected that the product is not damaged or the fault was caused by a wrong manoeuvring...

Страница 13: ...ximum permissible current of the manual bypass switch 16 A 40A 63A Selective output breakers IEC connectors 2 Maximumpermissiblevoltageoftheoutputbreakers 250 V Output breaker size 10 A Number of outp...

Страница 14: ...14 SALICRU...

Страница 15: ...15 BM R Rack mounting manual bypass USER S MANUAL...

Страница 16: ...alicru_SA Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers Variable frequency drives The T...

Отзывы: