Before cleaning it is necessary to turn off the power supply and block the switch to prevent accidental turning on while working.
It is necessary to wait until any mechanical motion stops, the engine cools down and the capacitors discharge.
Make sure that the fan and its parts and accessories are firmly and rigidly mounted.
The impeller has to be cleaned with caution in order not to damage the balance of the impeller.
It is strictly forbidden to use mechanical scrubs, chemicals, cleaners, compressed air stream or any liquids to clean the impeller.
It is prohibited to wash the fan with any liquids.
When the device’s maintenance is complete, mount it back to the air duct system performing same actions as pointed out in „installation“ and
„starting“ points and follow other requirements listed in this document.
DEFECTS AND THEIR ELIMINATION
Defect elimination works can only be performed by trained and qualified personnel.
If the device turns off, it is necessary to:
Check whether the network voltage and current meets the requirements indicated on the product label.
Check whether the electrical current reaches the device.
When the electrical power problems are eliminated, re-activate the device.
If the power current supply is in order but the device does not start, do the following:
Wait 10-20 min. until the engine cools down.
If the electrical current was not disconnected and after 10-20 min. the engine starts itself, this means that an automatic thermal protection was
triggered. It is necessary to look for engine overheating cause and eliminate it.
If the engine does not start after 10-20 min. do the following:
Disconnect the power supply.
Wait until any mechanical rotation stops, the engine cools down and the capacitors discharge.
Make sure that the impeller is not blocked.
Check the capacitor (for single-phase fans according to connection scheme). If the defects persist, replace the capacitor.
If that does not help, contact the supplier.
DIMENSIONS AND WEIGHT
M
M
VSA
øD
H
h
L
ød
ød1
M
M1
n
m
[mm]
[mm]
[mm]
[mm]
[mm]
[mm]
[mm]
[mm]
[mm]
[kg]
190 L 3.0
344
207
107
305
177
6,1
96,5
123,5
245
4,4
190 S 3.0
344
207
107
305
177
6,1
96,5
123,5
245
4,4
220 M 3.0
450
214,55
109
405
230
7,1
138
168
330
6,7
220 S 3.0
450
214,35
109
405
203
7,1
138
168
330
6,7
225 L 3.0
450
245,55
109
405
230
7,1
138
168
330
7,6
250 L 3.0
450
245,55
109
405
230
7,1
138
168
330
7,9
190 EKO
344
234
107
305
177
M4
96,5
123,5
245
4,5
220 EKO
450
241
109
405
230
M5
138
168
330
7
225 EKO
450
245,5
109
405
230
M5
138
168
330
7,6
250 EKO
450
315
109
405
230
M5
138
168
330
TECHNICAL DATA
VSA 3.0
190 L
190 S
220 M
220 S
225 L
250 L
- phase/voltage
[50 Hz/VAC]
~1,230
~1, 230
~1, 230
~1, 230
~1, 230
~1, 230
- power
[kW]
0,049
0,074
0,067
0,106
0,133
0,221