MAINTENANCE

The fan is fitted with maintenance-free ball bearings. The only maintenance required is cleaning of the impeller. We recommend inspection of the 

impeller every six months. Before cleaning disconnect the fan from the mains and block the mains switch. Remove the fan. Do not obstruct fan‘s 

balance. Do not use strong detergents or cleaning agents for cleaning. Internal insulation may be wiped with a damp cloth.

In the case of breakdown:

1. Check the mains power is reaching the fan.

2. Disconnect from the mains and ensure that the impeller is not blocked.

3.  If the thermo-contact has been activated, turn off the mains power. Wait until the motor chills and reconnect the mains power.

4. Check if the capacitor is connected (single-phase, refer to the wiring diagram).

5. If the fault persists, change the capacitor. If that does not help, contact the supplier. 

DIMENSIONS AND WEIGHT

VKSA

B

B1

B2

B3

H

H1

H2

H3

L

L1

m

[mm]

[mm]

[mm]

[mm]

[mm]

[mm]

[mm]

[mm]

[mm]

[mm]

[kg]

400x200-4-L1

400

420

440

507

200

220

240

338

417

445

21

400x200-4-L3

400

420

440

507

200

220

240

338

417

445

21

500x250-4-L1

500

520

540

605

250

270

290

393

502

530

23

500x250-4-L3

500

520

540

605

250

270

290

393

502

530

23

500x300-4-L1

500

520

540

605

300

320

340

443

532

560

28

500x300-4-L3

500

520

540

605

300

320

340

443

532

560

28

600x300-4-L1

600

620

640

705

300

320

340

443

612

640

37

600x300-4-L3

600

620

640

705

300

320

340

443

612

640

37

600x350-4-L1

600

620

640

705

350

370

390

493

672

700

47

600x350-4-L3

600

620

640

705

350

370

390

493

672

700

47

700x400-4-L3

700

720

740

811

400

420

440

562

752

780

78

800x500-6-L3

800

820

840

911

500

520

540

662

852

880

59

TECHNICAL DATA

VKSA

400x200-

4-L1

400x200-

4-L3

500x250-

4-L1

500x250-

4-L3

500x300-

4-L1

500x300-

4-L3

Max. airflow

[m

3

/h]

1079

1090

1651

1665

1883

2647

Max. pressure

[Pa]

226

233

312

330

383

386

Power consumption

[kW]

0,36

0,31

0,51

0,56

0,69

0,93

Current

[A]

1,80

0,51

2,30

0,95

3,00

1,90

Capacitor

[µF]

5

-

8

-

10

-

Revolution speed

[min

-1

]

1180

1230

1250

1270

1190

1380

Max air temp.

[C

o

]

40

70

40

40

40

50

Voltage / Frequency

[V/Hz]

230/50

400/50

230/50

400/50

230/50

400/50

VKSA

600x300-

4-L1

600x300-

4-L3

600x350-

4-L1

600x350-

4-L3

700x400-

4-L3

800x500-

6-L3

Max. airflow

[m

3

/h]

2882

3800

4478

5056

6300

7250

Max. pressure

[Pa]

485

533

650

646

830

472

Содержание VKSA

Страница 1: ...VKSA EN MOUNTING AND INSTALLATION INSTRUCTION...

Страница 2: ...wired with thermo contact leads and protectors If speed controller is used a separate thermo contact relay is not needed The fan can be installed in any position Not recommended the fan is not designe...

Страница 3: ...L3 400 420 440 507 200 220 240 338 417 445 21 500x250 4 L1 500 520 540 605 250 270 290 393 502 530 23 500x250 4 L3 500 520 540 605 250 270 290 393 502 530 23 500x300 4 L1 500 520 540 605 300 320 340 4...

Страница 4: ...1 15 1 50 2 40 2 50 3 70 2 70 Current A 5 10 2 60 11 00 4 10 6 00 4 90 Capacitor F 16 35 Revolution speed min 1 1210 1310 1340 1300 1320 830 Max air temp Co 40 40 40 40 40 50 Voltage Frequency V Hz 23...

Страница 5: ...te m3 s 0 41 0 49 0 59 0 9 Effective electric power input kW 0 53 0 76 1 05 1 01 SFPint W m3 s N A N A Face velocity m s 0 0 0 0 Normal external pressure Pa 490 642 781 490 Internal pressure drop of v...

Страница 6: ...risk reduction LST EN 60204 1 Safety of machinery Electrical equipment of machines Part 1 General requirements LST EN 60335 1 Household and similar electrical appliances Safety Part 1 General require...

Страница 7: ...uipment to manufacturer Delivery costs should be covered by customer Manufacturer reserves the right to change this technical passport any time without prior notice if some typographic errors or inacc...

Страница 8: ...00193 UNIT S MAINTENANCE TABLE Product name gu lu number Instalation Interval Date Fan cleaning Once a year Heat exchanger cleaning Once a year Filter replacement Every 3 4 months Look at the product...

Отзывы: