34
| DE
SMARTY XV v2019.06
N(L1)
PE
43
2
1
230VAC
ON
/O
FF
N
L1
L1
M3
PE
PE
DO4 (L(L2))
DO3 (L(L2))
230VAC
ON
/O
FF
N
L1
L1
M2
21.11. CONNECTION OF REMOTE CONTROL PANEL OR MODBUS
Wiring diagram.
Automation controller F zone, X18 connector.
Switch positions for X18 connector configuration
Switch
Position
Purpose
S2
1
A+Y (RS422->RS485)
2
B+Z (RS422->RS485)
3
120R line termination resistor
4
1kR line pull-up resistor
5
1kR line pull-down resistor
6
Galvanic isolation disable (turn ON when connecting Remote Controller - RS_GND will be shorted to GND,
OFF - when connecting to BMS)
21.12. OPERATION AND ALARM INDICATION (SMARTY X V 1.1)
Wiring diagram.
Automation controller B zone, X21 connector.
+24VDC
DO1
DO2
+24VDC
12
3
4
Al
ar
m
in
d
ica
tion
ou
tput
(STO
P)
Workin
g
in
d
ica
tion
ou
tput
(STA
RT
)
H2
H1
21.13. FIRE PLACE CONNECTION (SMARTY X V 1.1)
Wiring diagram.
Automation controller C zone, X23 connector.
1234
5678
-Fire Place II
DI4
+1
2V
DC
+1
2V
DC
DI3
-Fire Place I